Commissioning
5.4 Quick commissioning with a PC
Motor identification:
● [1]: Recommended setting. Measure the motor data at standstill and with the motor rotating.
The inverter switches off the motor after the motor data identification has been completed.
● [2]: Measure the motor data at standstill. The inverter switches off the motor after the motor
data identification has been completed.
Select this setting if the motor cannot freely rotate, e.g. for a mechanically limited traversing
range.
● [3]: Measure the motor data while the motor is rotating. The inverter switches off the motor
after the motor data identification has been completed.
● [11]: The same setting as [1]. The motor accelerates to the currently set setpoint after the
motor data identification.
● [12]: The same setting as [2]. The motor accelerates to the currently set setpoint after the
motor data identification.
142
Configuring encoders (Page 147)
Converter with the CU250S-2 Control Units
Operating Instructions, 04/2018, FW V4.7 SP10, A5E31759476B AG