Pulse Output / PWM Output Function
9.4.4 Setting Example of PWM Output
Overview
The PWM output is performed. It is controlled by the switch input (X140/X141) connected to
the 32-point input unit. If the start input (X141) turns on when the enable input (X140) is on,
the PWM output will start.
0 V (24 V DC)
(PWM0 EN)
X140
(PWM0 ST)
X141
Configuration
• Set the PWM output to the output (Y108).
• Select "PWM output" in the "Pulse output Advanced " dialog box, and input a frequency and
duty.
• For changing the frequency or duty ratio during the output, select "When start signal rises or
when data is updated" or "When start signal rises or when comparison output is performed"
for Data update timing.
9-18
Multi I/O Unit
WX10-WX13
WX14
WY10-WY13
32-point Input Unit
Y108 (PWM0)
Y118 (PWM0 EN)
Y11C (PWM0 ST)