Unit Allocation

4.1 Unit Allocation

4.1.1 Number of Occupied I/O Points for the Unit

The input and output starts from the same I/O numbers in FP7 series. For the multi I/O unit,
the following number of words is occupied.
Product number
AFP7MXY32DWD
AFP7MXY32DWDH

4.1.2 Confirmation of I/O Allocation Information

The following I/O contacts are allocated for the multi I/O unit. The external inputs and external
outputs that are not allocated to any functions can be used as general inputs and outputs.
 Input contact
Section
I/O no.
X0-X7
External input
X8-XF
X10-X17
X18-X1F
X20-X27
Internal input
for control
X28-X2F
X30-X3B
X30-X3F
(Note 1): The I/O numbers actually allocated are based on the starting word number allocated to the unit.
Example) When the starting word number for the unit is "10", input contacts are numbered starting from X100.
4-2
Name
FP7 Multi Input/Output Unit
FP7 Multi Input/Output Unit (H type)
Function
Counter (Input, reset mask) or positioning input
Interrupt input or counter (Input, reset, mask) or positioning input
Comparison contact monitor
Pulse output / PWM output monitor
Counter (Overflow flag, underflow flag)
(Reserved for system)
Positioning (Busy flag, operation done flag, home return done flag)
(Reserved for system)
Input
Output
4 words (64 points)
4 words (64 points)
6 words (96 points)
6 words (96 points)