3.3.4 Output Range Setting Area

When an output range setting is entered, the analog output range is set.
Applicable model
Model
AFPXHEDA4
AFPXHEA21
Output range setting value
H1: 0 to +10 V
H2: 0 to +5 V
H3: 0 to +20 mA
H4: -10 to +10 V
H5: -5 to +5 V
H6: +1 to +5 V
H7: +4 to +20 mA
H0, H8 to F: Do not use the analog input.
I/O allocation
Channel
CH0 to CH3
I/O contents
The range setting data for each channel data is allocated from the lower level in the order of
CH0, CH1, CH2, and CH3.
WUME-FPXHAIO-01
Expansion location
1st unit
2nd unit
3rd unit
WY36
WY46
WY56
3.3 Stored Data of the Output Contact (WY)