10.7 Stop Control
10.7.1 Type of Stop Operations
Type of stop operations
Name
Time chart
f[Hz]
System stop
f[Hz]
Emergency
stop
f[Hz]
Limit stop
f[Hz]
Deceleration
stop
E
Emergency stop deceleration time
E
Limit stop deceleration time
E
Deceleration time
E
Occurrence condition and
operation
Once the system stop contact (Y44)
turns on, an active operation will stop and
the pulse outputs of all channels will
immediately stop.
The similar operation is performed
when the operation mode of the control
unit is switched from RUN to PROG.
t[ms]
Once an emergency stop contact (Y48-
Y4B) turns on, an active operation will
stop and the pulse outputs of
corresponding channels will stop.
Performs a deceleration stop in the
emergency stop deceleration time
specified in the positioning parameter
setting menu of Configurator PMX.
The specified time is a deceleration time
t[ms]
from 500 kHz.
Once the limit + input or limit - input
(X2, X3, X6, X7, XA, XB, XE, XF) turns
on, an active operation will stop and the
pulse outputs of corresponding channels
will stop.
Performs a deceleration stop in the
limit stop deceleration time specified in
the positioning parameter setting menu of
Configurator PMX.
The specified time is a deceleration time
t[ms]
from 500 kHz.
Once a deceleration stop contact
(Y4C-Y4F) turns on, an active operation
will stop and the pulse outputs of
corresponding channels will stop.
Performs a deceleration stop in the
deceleration time specified for the active
positioning operation.
t[ms]
10.7 Stop Control
10-31