13.4.2 Input Setting

 Input setting
Unit
memory no.
Name
(Hex)
Input voltage /
Input time
UM00100
constant setting
(X0-X7)
Input voltage /
Input time
UM00101
constant setting
(X8-XF)
Allocation of unit memories
UM no.
Bit no.
b15-b12
I/O number
XF,XE,XD,XC
Input voltage
I/O number
Input time
XF,XE
constant
Setting value
Initial value
H 2
(Hex)
They are set by writing the following values which indicate the input voltage and input time
constant for two inputs to the four bits of each unit memory. When allocating them using the
tool software, it is not necessary to write them.
Setting
Input
value
voltage
H0
H1
H2 (Default)
H3
5V-24V mode
H4
H5
H6
H7
Precautions when making settings with programs
• Input voltage should be set in increments of four external input terminals (four groups).
• When the voltage settings of the higher two groups and lower two groups of input voltage
are different, the 5V-24V mode takes priority.
• Input time constant should be set in increments of two external input terminals (eight groups).
• As the input voltage and input time constant are set for external input terminals, the settings
are effective after the allocation of each function corresponding to inputs X0 to XF.
13-28
Default
Setting range and description
H 2222
Set values indicating input voltage and input time
constant.
H 2222
UM00101
b11-b8
b7-b4
XB,XA,X9,X8
XD,XC
XB,XA
H 2
H2
Input time
constant
Effective
pulse width
0
1 µs
2 µs
4 µs
8 µs
16 µs
2 ms
4 ms
b3-b0
b15-b12
b11-b8
X7,X6, X5,X4
X9,X8
X7,X6
X5,X4
H2
H2
Setting
Input
value
voltage
H8
H9
HA
HB
12V-24V mode
HC
HD
HE
HF
R
A
UM00100
b7-b4
b3-b0
X3,X2, X1,X0
X3,X2
X1,X0
H2
H2
H2
Input time
constant
Effective
pulse width
0
1 µs
2 µs
4 µs
8 µs
16 µs
2 ms
4 ms
W
A