Pulse Output / PWM Output Function
9.4 Execution Example of Pulse Output / PWM Output
Function
9.4.1 Setting Example of Pulse Output
Overview
The pulse output is performed in the direction distinction mode. It is controlled by the switch
input (X140/X141/X142) connected to the 32-point input unit. If the start input (X141) turns on
when the enable input (X140) is on, the pulse output will start. The pulse output is switched to
that of the reverse direction by turning on X142.
0 V (24 V DC)
(PLS0 EN)
X140
(PLS0 ST)
X141
(PLS0 DIR)
X142
Configuration
• Set the pulse output to the outputs (Y108-Y109).
• Select "PLS output - Direction distinction" in the "Pulse output Advanced " dialog box, and
input a frequency.
• Select "When start signal rises" for the data update timing.
9-12
Multi I/O Unit
WX10-WX13
WX14
WY10-WY13
32-point Input Unit
Y118 (PLS0 EN)
Y11C (PLS0 ST)
Y128 (PLS0 DIR)
Y108 (PLS0 A)
Y109 (PLS0 B)