・The retry interval is set with parameter "P026: Waiting Time".
・ Fault alarm is not output during retry operation. But when the fault still
occurs even if retry is performed for preset times, the fault alarm will be
output.
・If an unselected fault occurs during retry, the fault alarm will be output and
the retry count accumulated till present will be cleared.
・Once the power is cut off, the retry count accumulated till now will be
cleared.
・If the fault does not occur for over 5 minutes, the retry times accumulated up
to now will be cleared.
・When speed search is selected with parameter "P165: Speed Search Select
during Retry" and the time set with parameter "P026: Waiting Time" and "P163:
Waiting Time to Speed Search" has elapsed, the speed search function will
start to operate.
■ Related parameter: P026
P024

Start Mode

This parameter is used to set the start-up operation for the case that a run
signal set externally is input when the power is turned ON.
Depending on the start mode setting, when the run
signal is ON, the inverter may start (restart) suddenly if
the power is turned ON or restored after a power failure.
Therefore, do not approach the unit. Design the machine
so that personal safety can be ensured even if the inverter
starts suddenly.
Depending on the start mode function setting, if the fault
trip is reset with the run signal ON, the inverter may
sometimes restart suddenly. (Please take measures to
ensure personal safety.)
Failure to do so may lead to injury.
Appendix Function Parameter List
163