Panasonic S-160PE1R5A Technical Data And Service Manual

Panasonic S-160PE1R5A Technical Data And Service Manual

R410a dc inverter, indoor/outdoor units
Table of Contents

Advertisement

O rder N o. SB PAC1712007CE
TEC H N IC A L D A TA  & S ER V IC E M A N U A L
Indoor U nit
O utdoor U nit
Ty p e E1
S- 160PE1R 5A
Ty p e E3
S- 180PE3R 5, S- 200PE3R 5, S- 224PE3R 5
U - 160PE2R 8A, U - 180PE2R 8A, U - 200PE2R 8A, U - 224PE2R 8A
.
S M 830262-00
R EFER EN C E N O

Advertisement

Table of Contents
loading

Summary of Contents for Panasonic S-160PE1R5A

  • Page 1 O rder N o. SB PAC1712007CE TEC H N IC A L D A TA  & S ER V IC E M A N U A L Indoor U nit O utdoor U nit Ty p e E1 S- 160PE1R 5A Ty p e E3 S- 180PE3R 5, S- 200PE3R 5, S- 224PE3R 5 U - 160PE2R 8A, U - 180PE2R 8A, U - 200PE2R 8A, U - 224PE2R 8A...
  • Page 2 • Connect all wiring tightly. oose wiring may cause overheating at connection points and a possible fire hazard. This air conditioner must be installed by the sales dealer Provide a power outlet to be used or installer. exclusively for each unit. This information is provided for use only by authorized persons.
  • Page 3 …In Moist or Uneven Locations • Keep all tubing runs as short as Use a raised concrete pad or concrete possible. blocks to provide a solid, level foundation • Use the flare method for connecting for the outdoor unit. This prevents water tubing.
  • Page 4 CAUTI N CAUTION • Ventilate any enclosed areas when installing or testing the refrigeration system. eaked refrigerant gas, on contact with fire or heat, can produce dangerously toxic gas. • Confirm after installation that no refrigerant gas is leaking. If the gas comes in contact with a burning stove, gas water heater, electric room heater or other heat source,...
  • Page 5 Check of Density Limit The standards for minimum room volume are as follows. (1) No partition (shaded portion) The room in which the air conditioner is to be installed requires a design that in the event of refrigerant gas leaking out, its density will not exceed a set limit. The refrigerant (R410A), which is used in the air conditioner, is safe, without the toxicity or combustibility of ammonia, and is not restricted by laws imposed to protect the ozone layer.
  • Page 6: Table Of Contents

    — — CONTENTS — — Section 1. SPECI FI CA TI ONS ....................1-1 1-1. U nit Specif ications .........................1-2 1-2. M aj or Component Specif ications ..................1-6 ..................1-14 1-3 . Other Component Specif ications 1-4. D imensional D ata .........................1-18 1-5 .
  • Page 7 Section 7. REMOTE CONTROLLER FUNCTIONS SECTION..........7-1. Simple Settings Function ....................7-2. List of Simple Setting Items....................7-3. Detailed Settings Function ....................7-4. List of Detailed Setting Items ....................7-5. Simple Setting Items ......................7-6. Detailed Setting Items ......................7-10 7-7.
  • Page 8 – MEMO –...
  • Page 9 1. SPECIFICATIONS 1-1. Unit Specifications ..................... 1-2 1-2. Major Component Specifications ................1-6 1-3. Other Component Specifications ................1-14 1-4. Dimensional Data ..................... 1-18 1-5. Refrigerant Flow Diagram ..................1-22 1-6. Operating Range ...................... 1-23 1-7. Capacity Correction Graph According to Temperature Condition .....1-24 1-8. Noise Criterion Curves ....................1-26 1-9. Indoor Fan Performance..................1-29 1-10. ELECTRICAL WIRING ....................1-34 1-11. Installation Instructions ..................1-41 Š Outdoor Unit 1. Tubing Length ..........................1-41 2. Check of limit density .........................1-42 3. SELECTING TH E INSTALLATION SITE ..................1-43 4.
  • Page 10: Unit Specifications

    Single-Type 1-1. Unit Specifications Ducted Type S-160PE1R5A / U-160PE2R8A INDOOR M ODEL S-160PE1R5A PANEL M ODEL OUTDOOR M ODEL U-160PE2R8A Branch pipe M ODEL Performance test condition ISO13253 / AS / NZS3823.1 ø , H z 1ø 50H z 3ø 50H z Power supply 230V 240V...
  • Page 11 Single-Type High Static Pressure Ducted Type S-180PE3R5 / U-180PE2R8A INDOOR M ODEL S-180PE3R5 PANEL M ODEL OUTDOOR M ODEL U-180PE2R8A Branch pipe M ODEL Performance test condition ISO13253 / AS / NZS3823.1 ø , H z 1ø 50H z 3ø 50H z Power supply 220V 230V 240V 380V 400V 415V...
  • Page 12 Single-Type High Static Pressure Ducted Type S-200PE3R5 / U-200PE2R8A INDOOR M ODEL S-200PE3R5 PANEL M ODEL OUTDOOR M ODEL U-200PE2R8A Branch pipe M ODEL Performance test condition ISO13253 / AS / NZS3823.1 ø , H z 1ø 50H z 3ø 50H z Power supply 220V 230V 240V 380V 400V 415V...
  • Page 13 Single-Type High Static Pressure Ducted Type S-224PE3R5 / U-224PE2R8A INDOOR M ODEL S-224PE3R5 PANEL M ODEL OUTDOOR M ODEL U-224PE2R8A Branch pipe M ODEL Performance test condition ISO13253 / AS / NZS3823.1 ø , H z 1ø 50H z 3ø 50H z Power supply 220V 230V 240V 380V 400V 415V...
  • Page 14: M Aj Or Component Specif Ications

    1-2. M aj or Component Specif ications (A ) I ndoor U nits D ucted Ty pe S-16 0 PE1R5 A M OD EL No. S-16 0 PE1R5 A Source 230 - 240V , single-phase, 50H z Controller P.C.B. A ss' y C39 37-840-1Y Fan (Number...diameter) SIROCCO(2 / Ø...
  • Page 15 1-2. M aj or Component Specif ications (A ) I ndoor U nits High Static Pressure D ucted Ty pe S-18 0 PE3 R5 M OD EL No. S-18 0 PE3 R5 Source 230 - 240V , single-phase, 50H z Controller P.C.B.
  • Page 16 (A ) I ndoor U nits High Static Pressure D ucted Ty pe S-20 0 PE3 R5 M OD EL No. S-20 0 PE3 R5 Source 230 - 240V , single-phase, 50H z Controller P.C.B. A ss' y ACX A73C22170 Fan (Number...diameter) SIROCCO (2...ø...
  • Page 17 (A ) I ndoor U nits High Static Pressure D ucted Ty pe S-224PE3 R5 M OD EL No. S-224PE3 R5 Source 230 - 240V , single-phase, 50H z Controller P.C.B. A ss' y ACX A73C22170 Fan (Number...diameter) SIROCCO (2...ø 250) Fan motor DM UB8D4AC...750W M odel...Nominal output...
  • Page 18 (B) Outdoor U nits U -16 0 PE2R8 A M OD EL No. U-160PE2R8A 400/415V  3-Phase 50H z Source Controller P.C.B. A ss' y ACX A73C07280 Control circuit fuse Compressor M odel..number 5J D 650X DB22 520V  DC M OTOR Source Nominal output 4,200 Compressor oil...
  • Page 19 (B) Outdoor Units U-180PE2R8A U-180PE2R8A MODEL No. 400/415V 3-Phase 50Hz Source ACXA73C07280 Controller P.C.B. Ass'y Control circuit fuse Compressor Model..number 5JD650XDB22 Source 520V DC MOTOR Nominal output 4,200 Compressor oil 2,050 Coil resistance Ω U-V 0.678  U-W 0.700  V-W 0.691 (Ambient temperature 25°C) Safety control Discharge temperature control –...
  • Page 20 (B) Outdoor Units U-200PE2R8A U-200PE2R8A MODEL No. 400/415V 3-Phase 50Hz Source ACXA73C07260 Controller P.C.B. Ass'y Control circuit fuse Compressor Model..number 5JD650XDB22 Source 520V DC MOTOR Nominal output 4,800 Compressor oil 2,050 Coil resistance Ω U-V 0.678  U-W 0.700  V-W 0.691 (Ambient temperature 25°C) Safety control Discharge temperature control –...
  • Page 21 (B) Outdoor Units U-224PE2R8A MODEL No. U-224PE2R8A Source 400/415V 3-Phase 50Hz Controller P.C.B. Ass'y ACXA73C07260 Control circuit fuse Compressor Model..number 5JD650XDB22 Source 520V DC MOTOR Nominal output 5,500 Compressor oil 2,050 Coil resistance Ω U-V 0.678  U-W 0.700  V-W 0.691 (Ambient temperature 25°C) Discharge temperature control Safety control –...
  • Page 22: Other Component Specif Ications

    1-3 . Other Component Specif ications Outdoor U nits U -16 0 PE2R8 A M OD EL No. Outdoor Unit U-160PE2R8A Power Transf ormer Rated – Source V AC, H z – – Secondary – Coil resistance – – Thermal cut off temperature Thermistor (Coil / A ir sensor): TH1, TH2, TH3 , TH4 -20°C: 38.48±...
  • Page 23 1-3. Other Component Specifications Outdoor Units U-180PE2R8A Outdoor Unit U-180PE2R8A MODEL No. Power Transformer Rated – Source VAC, Hz – – Secondary – Coil resistance Ω – Thermal cut off temperature – Thermistor (Coil / Air sensor): TH1, TH2, TH3, TH4 Resistance kΩ...
  • Page 24 Outdoor Units U-200PE2R8A Outdoor Unit U-200PE2R8A MODEL No. Power Transformer Rated – Source VAC, Hz – – Secondary – Coil resistance Ω – – Thermal cut off temperature Thermistor (Coil / Air sensor): TH1, TH2, TH3, TH4 Resistance kΩ -20°C: 38.48±2%     20°C: 6.517±2% -10°C: 23.67±2%     30°C: 4.448±2% 0°C: 15.00±2%     40°C: 3.100±2% 5°C: 12.06±2%     45°C: 2.607±2%...
  • Page 25 Outdoor Units U-224PE2R8A Outdoor Unit U-224PE2R8A MODEL No. Power Transformer Rated – Source VAC, Hz – – Secondary – Coil resistance Ω – – Thermal cut off temperature Thermistor (Coil / Air sensor): TH1, TH2, TH3, TH4 Resistance kΩ -20°C: 38.48±2%     20°C: 6.517±2% -10°C: 23.67±2%     30°C: 4.448±2% 0°C: 15.00±2%     40°C: 3.100±2% 5°C: 12.06±2%     45°C: 2.607±2%...
  • Page 26: D Imensional D Ata

    1-4. D imensional D ata (A ) I ndoor U nits: D ucted Ty pe (Ty pe E1) POSITION OF SUSPENSION BOLT unit : mm 1160 1100 unit : mm Refrigerant liquid tubing (Flare) ø 9 .52 Refrigerant gas tubing (Flare) ø 19 .05 Air intake duct connecting side flange Air discharge duct connecting side flange Drain port...
  • Page 27 (A ) Indoor U nits: H igh S tatic Pressure D ucted Type (Type E3) R eq uired M inimum S pace for Installation and S erv ice (1) D imensions of suspension b olt pitch and unit U nit: mm 1006 554 (Suspension b olt pitch)
  • Page 28 (B) Outdoor Unit: U-160PE2R8A, U-180PE2R8A Unit: mm Mounting hole (4-R6.5), anchor bolt : M10 Refrigerant tubing (liquid tube), Air intake flared connection (ø9.52) Refrigerant tubing (gas tube), (10) flared connection (ø19.05) Refrigerant tubing port Electrical wiring port (ø13) Electrical wiring port (ø22) Air intake Electrical wiring port (ø27) Electrical wiring port (ø35)
  • Page 29 (B) Outdoor Unit: U-200PE2R8A, U-224PE2R8A Unit: mm Mounting hole (4-R6.5), anchor bolt : M10 Refrigerant tubing (liquid tube), Air intake flared connection (ø12.7) (10) Refrigerant tubing (gas tube), flared connection (ø19.05)* Refrigerant tubing port Electrical wiring port (ø13) Electrical wiring port (ø22) Air intake Electrical wiring port (ø27) Electrical wiring port (ø35)
  • Page 30: Refrigerant Flow Diagram

    1-5. Refrigerant Flow Diagram Cooling cycle Heating cycle Indoor Unit : S-160PE1R5A Outdoor Unit : U-160PE2R8A, U-180PE2R8A S-180PE3R5 High pressure switch Gas line 4-way valve service valve 19.05 Oil separater Flare connection Muffler Strainer Outdoor-air Suction Temp Temp Thermistor Thermistor...
  • Page 31: Operating Range

    1-6 . Operating Range S-16 0 PE1R5 A − U -16 0 PE2R8 A S-18 0 PE3 R5 − U -18 0 PE2R8 A S-20 0 PE3 R5 − U -20 0 PE2R8 A S-224PE3 R5 − U -224PE2R8 A Temperature Indoor air intake temp.
  • Page 32: Capacity Correction G Raph A Ccording To Temperature Condition

    1-7. Capacity Correction Graph According to Temperature Condition U-160PE2R8A / U-180PE2R8A / U-200PE2R8A / U-224PE2R8A (For 50 Hz) Cooling capacity ratio (maximum capacity) Heating capacity ratio (maximum capacity) Indoor air intake temp (WB) Indoor air intake temp ( °C 22WB 19WB 16WB °C...
  • Page 33 U -160PE2R 8A R ated capacity ratio for cooling R ated capacity ratio for h eating 139% 131% Capacity (W ) Capacity (W ) U -180PE2R 8A R ated capacity ratio for cooling R ated capacity ratio for h eating 124% 113% Capacity (W )
  • Page 34: Noise Criterion Curv Es

    1-8 . Noise Criterion Curv es H igh Static Pressure Ducted Type H IG H : S-180PE3R5 M ODEL : S-160PE1R5A M ODEL SOUND LEV EL H IG H 51 dB(A) SOUND LEV EL : H IG H 46 dB(A)
  • Page 35 COOLING HEATING MODEL : U-160PE2R8A : U-160PE2R8A MODEL SOUND LEVEL : 59 dB(A) SOUND LEVEL : 61 dB(A) CONDITION : 1 m in front at height of 1.5 m CONDITION : 1 m in front at height of 1.5 m NC-70 NC-70 NC-60...
  • Page 36 HEATING COOLING : U-200PE2R8A : U-200PE2R8A MODEL MODEL SOUND LEVEL : 60 dB(A) SOUND LEVEL : 60 dB(A) CONDITION : 1 m in front at height of 1.5 m CONDITION : 1 m in front at height of 1.5 m NC-70 NC-70 NC-60...
  • Page 37: I Ndoor Fan Perf Ormance

    1-9. I ndoor Fan Perf ormance Ty pe E1 S-16 0 PE1R5 A curv e 20.0 30.0 40.0 50.0 60.0 70.0 Air V olume (m /min) 1-29...
  • Page 38 Type E3 External S tatic Pressure S etting Choose one of the methods (selection of “a”, “b”, “c” within the range of dotted line as shown in the flowchart below) and mak e settings. a. N o setting changes: W hen using as it is f actory preset at shipment. (If resetting after external static pressure setting once, it might be different from factory preset.) b .
  • Page 39 1-9-1. How to Set on PC Board 1. Turn off the power breaker to halt the supply of electricity to the PC board. 2. Open the lid of the electrical component box and confirm the location where the Select switch on the indoor unit control PCB is placed.
  • Page 40 1-9-3. O perating th e H igh -spec W ired R emote 3. Select the “Code no. ” b y pressing the C ontroller (C Z -R TC 5A / C Z -R TC 5B ) b utton. Change the “Code no. ” to “5D ” b y pressing the b utton (or k e eping it pressed).
  • Page 41 1-9-4. Indoor Fan Performance Cooling Heating Cooling Item code “ ” Heating Cooling Setting at shipment Heating Type 180 (External static pressure 60 Pa) (External static pressure 100 Pa) (External static pressure 150 Pa) 55 60 65 70 75 80 85 75 80 50 55 60 65 70 75 80 85...
  • Page 42: El Ectri Ca L Wi Ri Ng

    1-10. EL EC TR IC A L W IR IN G G eneral Precautions on W iring B ef ore w iring, conf irm the rated v o ltage of the unit as show n on its nameplate, then carry out the w iring closely f ollow ing the w iring diagram.
  • Page 43 Wiring Sy stem D iagrams < Ty pe E1> Indoor unit Power supply Outdoor unit 230-240V ~ 50 H z INV unit Power supply G round Remote 400-415V , 3 N~ , 50 H z controller WH T G round (SG : Shows the ground for the shielded cable.) <...
  • Page 44 <Type E1> CAUTION (1) When linking the outdoor units in a network, disconnect the terminal extended from the short plug from all outdoor units except any one of the outdoor units. (When shipping: In shorted condition.) For a system without link (no wiring connection between outdoor units), do not remove the short plug. (2) Do not install the inter-unit control wiring in a way that forms a loop.
  • Page 45 < Ty pe E3 > CA U TI ON (1) When link ing the outdoor units in a network , disconnect the terminal extended f rom the short plug f rom all outdoor units except any one of the outdoor units. (When shipping: I n shorted condition.) For a sy stem without link (no wiring connection between outdoor units), do not remov e the short plug.
  • Page 46 How to connect wiring to the terminal For stranded wiring Examples of shield wires (1) Cut the wire end with cutting pliers, then strip the insulation (1) Remove cable coat not to scratch braided shield. to expose the stranded wiring about 10 mm and tightly twist the wire ends.
  • Page 47 This air conditioner must be installed in accordance with national wiring regulations. Cables connected to outdoor unit must be approved polychloroprene sheathed type 60245 IEC 57 or H05RN-F/H07RN-F or heavier. The units must be connected to the supply cables for fi xed wiring by qualifi ed technician. Circuit breaker must be incorporated in the fixed wiring in accordance with the national wiring regulations.
  • Page 48 OUTDOOR UNIT/3-PHASE MODEL Power supply (220/230/240V~) Power supply (400/415V 3N~) c r i c r i Switch Switch Earth Control cable Earth Wired remote Indoor unit Outdoor unit controller This equipment complies with EN/IEC 61000-3-12 provided that the short-circuit power Ssc is greater than or equals to 1850 kVA at the interface point between the user’s supply and the public system.
  • Page 49: Installation Instructions

    1-11. Installation Instructions Outdoor Unit Tubing Length (A) Single type During tubing work, try to make both the tubing length (L) Single and the difference in elevation (H1) as short as possible. See the Table 1-4. Main tubing L Table 1-4 Tubing Data for Models (Single) Models U-160PE2R8A U-200PE2R8A...
  • Page 50: Check Of Limit Density

    Chec k of limit density When installing an air conditioner in a room, it is Minimum indoor volume & fl oor area relative to the necessary to ensure that even if the refrigerant gas amount of refrigerant are roughly as given in the accidentally escapes, its density does not exceed the following table.
  • Page 51: Selecting The Installation Site

    3. SELECTING THE INSTALLATION SITE The following parts are supplied as accessories with each outdoor unit. Check that all accessory parts are present before installing the outdoor unit. Part name Diagram Quantity Part name Diagram Quantity Joint piping A (ø19.05 → ø25.4) Protective bushing (for protecting electrical wires) Banding strap...
  • Page 52: Installation Service Space

    Please secure necessary space to guarantee performance and service & 4. INSTALLATION SERVICE SPACE maintenance. For multiple installations, please secure enough space to enable removal of side face screws between units. (unit: mm) Where there are obstacles at the intake Where there are obstacles at the discharge If upper part is open If upper part is open...
  • Page 53: Transport And Install The Outdoor Unit

    5 . TRANSPORT AND INSTALL THE OUTDOOR UNIT Transporting More than 40mm 1. Transport the outdoor unit in its original packaging as close as possible to the installation location. 2. In the event that the unit needs to be lifted or suspended, use a rope or belt and use cloth or wood as padding to avoid damaging the unit.
  • Page 54: Refrigerant Installation

    For indoor unit refrigerant piping installation, refer to the installation instruction 6. REFRIGERANT INSTALLATION manual that comes with that indoor unit. Do not reuse existing piping, install new piping. 1. Precautions during refrigerant installation. Use clean pipes with no dust inside. The pipe may corrode with the presence of fl...
  • Page 55 Precautions w hen operating the 3-w ay valve for piping installation Do not open the 3-way valve until the piping installation is completed. It is closed during shipment. During installation the side panel may warp if only the are nut is loosened and tightened with a torque wrench. As a result, always be sure to secure to the hexagonal part of the 3-way valve with a spanner, or other tool.
  • Page 56 Precautions for insulation installation Maximum temperature limit of gas or liquid piping exceeds 120 °C In high humidity environment, reinforce the insulation material for the refrigerant piping. Failure to do so may result in condensation on the surface of the insulation material. Use materials with good heat-resistant properties as the heat insulator for the pipes.
  • Page 57: Selecting The Location For Installation Service

    When installing multiple units, allow enough space in between the units and 7. SELECTING THE LOCATION FOR the side of the building. INSTALLATION SERVICE (unit: mm) Example of connecting pipe process (U-200PE2R8A/U-224PE2R8A) (1) Front mounting (2) Right mounting/flare processing Flare processing Flare processing Joint...
  • Page 58: Š Indoor Unit

    Indoor Unit 8. SELECTING THE INSTALLATION SITE CAUTION When moving the unit during or after unpacking, make sure to lift it by holding its lifting lugs. Do not exert any pressure on other parts, especially the refrigerant piping, drain piping and flange parts. If you think the humidity inside the ceiling might exceed 30°C and RH 80%, reinforce the insulation on the unit body.
  • Page 59: H Ow To Install Th E Indoor Unit

    9.HOW TO I NSTA L L THE I ND OOR U NI T < Ty pe E1> 9-1-1. Req uired M inimum Space f or I nstallation and Serv ice (1) D imensions of suspension bolt pitch and unit Provide a check port on the piping side ceiling for repair and maintenance. Install the indoor unit once the following conditions are satisfied and after receiving the customer approval.
  • Page 60 9-1-2. 1-6) 1-7). 1-10 1-3. 1-52...
  • Page 61 9-1-3. Installing the Drain Pipe 1-14 1-15) 1-11) 1-15 1-16) 1-11 1-16 9-1-4. Connecting Duct to indoor Unit 1-12) 1-12 1-13) 1-17 1-13 1-53...
  • Page 62 9-1-5. Indoor Fan Performance Type E1 S -160PE1R 5A curv e 20. 0 30. 0 40. 0 50. 0 60. 0 70. 0 Air Volume (m /min) 9-1-6. A ccessories S upplied w ith U nit 1-54...
  • Page 63 < Ty pe E3 > 9-2-1. When transporting the indoor unit to the roof space through the ceiling opening Transport is possible without separation with a ceiling opening dimension of over 500 × 1,150 mm and a roof space dimension as shown below.
  • Page 64 9-2-1-1. H ow to separate th e indoor unit 3. R emov e the motor relay connector. 1. R emov e the w iring cov e r. R emov e tw o motor relay connectors. (1) Loosen tw o screw s. Tw o screw s R emov e the w ire f rom the f ixed mounting b rack e t.
  • Page 65 9-2-1-2. H ow to assemb le th e indoor unit 1. Attach the f an motor unit. (1) Pass the b olts f or the heat exchanger unit through the round holes. Mount the unit w ith three holes located in the center of the upper side.
  • Page 66 9-2-2. Req uired M inimum Space f or I nstallation and Serv ice (1) D imensions of suspension bolt pitch and unit Unit: mm 1006 554 (Suspension bolt pitch) Inspection access (600× 600) (Field supply) M in. 69 0 (Space for service) Ceiling M in.
  • Page 67 9-2-3. S uspending th e Indoor U nit D epending on the ceiling ty p e: 1. Check the suspension b olt pitch. 2. Ensure that the ceiling is strong enough to support the w eight of the unit. 3. To prev e nt the unit f rom dropping, f irmly f asten the suspension b olts as show n in the f igure b elow . U nit: mm Hole- in- anchor Hexagonal nut (f ield supply )
  • Page 68 9-2-4. Installing the Refrigerant Tubing The size of the refrigerant tubing is as shown in the table below. Table 1-5 Type 200 / 224 ø19.05 (~ 30 m) ø19.05 Gas tube ø25.4 (Over 30 ~ 50 m) (Brazing connection) (Brazing connection) ø9.52 (Flare connection) ø12.7 (Flare connection) Tightening torque (approximate)
  • Page 69 (3) Ensure the drain pipe has a dow nw ard slant (1/100 or more). D ow nw ard slant Min. 1/100 C orrect Incorrect (4) The drain pipe w ith a trap should b e installed aw ay f rom the indoor unit. (5) D o not f orcib ly install the drain pipe to the indoor unit tub ing.
  • Page 70 Hose b and (supplied) D rain port (D rainage check section on drain port, transparent) Hard PVC pipe Sof t PVC sock et Sof t PVC sock et (VP25 f ield supplied) U nev en surf ace D rain hose (supplied) * Apply approx.
  • Page 71 9-2-7. External Static Pressure Setting Choose one of the methods (selection of “a”, “b”, “c” within the range of dotted line as shown in the flowchart below) and make settings. a. No setting changes: When using as it is factory preset at shipment. (If resetting after external static pressure setting once, it might be different from factory preset.) b.
  • Page 72 9-2-8 . How to Set on PC Board 1. Turn off the power breaker to halt the supply of electricity to the PC board. 2. Open the lid of the electrical component box and confirm the location where the Select switch on the indoor unit control PCB is placed.
  • Page 73 9-2-10. O perating th e H igh -spec W ired R emote 3. Select the “Code no. ” b y pressing the C ontroller (C Z -R TC 5A / C Z -R TC 5B ) b utton. Change the “Code no. ” to “5D ” b y pressing the b utton (or k e eping it pressed).
  • Page 74 9-2-11 . Indoor Fan Performance Cooling Heating Cooling Item code “ ” Heating Cooling Setting at shipment Heating Type 180 (External static pressure 60 Pa) (External static pressure 100 Pa) (External static pressure 150 Pa) 55 60 65 70 75 80 85 70 75 80 85 50 55 60...
  • Page 75 9-2-12. A ccessories S upplied w ith U nit Part N ame Figure Q ’ ty R emark s Special F or indoor unit suspension w asher Insulator F or gas and liq uid tub es D rain hose Hose b and F or securing drain hose D rain insulator...
  • Page 76: How To Process Tubing

    1-12. HOW TO PROCESS TUBING <Type E1, E3> The liquid tubing side is connected by a flare nut, and the gas tubing side is connected by brazing. 1. Connecting the Refrigerant Tubing Use of the Flaring Method Many of conventional split system air conditioners employ the flaring method to connect refrigerant tubes that run between indoor and outdoor units.
  • Page 77 Caution Bef ore Connecting Tubes Tightly (1) Apply a sealing cap or water-proof tape to prevent dust or water from entering the tubes before they are used. Apply refrigerant lubricant. (2) Be sure to apply refrigerant lubricant (ether oil) to the inside of the flare nut before making piping connections.
  • Page 78 3. Insulating th e R efrigerant Tub ing Tw o tub es arranged togeth er Tub ing Insulation Liq uid tub ing G as tub ing Thermal insulation must b e applied to all units tub ing, including distrib ution j oint (f ield supply ) . * F or gas tub ing, the insulation material must b e heat resistant to 120°...
  • Page 79: A Cu U Mpu Rg I

    1-13. VACUUM PURGING Leak Tightness Test Method Keep 3-way valve fully closed and pressurize through 3-way valve service port. Do not pressurize to the default value at once. Pressurize gradually. 1 Pressurize to 0.5MPa (5kgf/cm ² G) and then leave it for 5 minutes Use nitrogen gas for the leak tightness test.
  • Page 80: Precautions Regarding Test Run

    1-15. PRECAUTIONS REGARDING TEST RUN Check Before Test Run Content check Power supply cable Is the wire set up and connected as described in the instructions? Check for any phase sequence. Indoor/outdoor Are the wire connection’s screws loose? Is the open and close device / leakage breaker installed? connection wire Is the power supply cable’s thickness and length appropriately measured as described in the instructions? Earth wire...
  • Page 81: Checks After Installation Have Completed

    1-16. CHECKS AFTER INSTALLATION HAVE COMPLETED Check the following items after completing installation. Is there a short circuit with the intake air fl ow? Is the insulation secure? (Refrigerant piping) Are there any errors with the wiring? Are the terminal screws loose? Tightening torque (Unit: N•m {kgf•m}) M4…...
  • Page 82: Supplement

    8 . Supplement 1-18 . Supplement 1. D imensions of A ir-D ischarge Chamber In snowy regions, if there is concern that snow may enter the air discharge chamber, remove the base of the chamber before using. Q ’ ty Ref erence diagram Upward, Air-discharge support Unit: mm...
  • Page 83 8 . Supplement Ref erence diagram f or U pward, side installation f ixture (f ield supply ) Unit: mm 2-ø 5 H OLE 585± 0.2 (1.6) (1.6) (1.6) (1.6) 608.2 Ref erence diagram f or U pward, L ouv er (f ield supply ) Unit: mm 610.4±...
  • Page 84 8 . Supplement Ref erence diagram f or U pward, L ouv er installation guide (f ield supply ) Unit: mm 9 0° ø 3.3± 0.05 ø 6.5 D TL A (S= 1:1) (2 POSI TI ON) 2-M 4 FUNNEL EX TRUDED H OLE (TH IS SURFACE 凸) 585±...
  • Page 85 8 . Supplement Ref erence diagram f or D ownward, Right side installation f ixture (f ield supply ) Unit: mm 6 2-ø 5 HOLE 615± 0.2 D TL A (S= 1:2) Ref erence diagram f or D ownward, L ef t side installation f ixture (f ield supply ) Unit: mm 2-ø...
  • Page 86 8 . Supplement Ref erence diagram f or D ownward, L ouv er (f ield supply ) Unit: mm 610.4± 0.2 Ref erence diagram f or D ownward, U pward installation f ixture (f ield supply ) Unit: mm (2.6) 605.2 (2.6) 605.2...
  • Page 87 8 . Supplement Ref erence diagram f or D ownward, D ownward installation f ixture (f ield supply ) Unit: mm D TL A (S= 1:2) 220.4 550.4 610.4± 0.2 1-79...
  • Page 88 8 . Supplement 2. D imensions of Wind-proof D uct Ref erence diagram Air Intake Unit: mm Air-discharge Air-discharge 9 80 (322.5) 41.5 Air-discharge Air-discharge Wind-proof Duct Air- Air- discharge discharge Wind-proof Duct Air- Air- discharge discharge Ref erence diagram f or wind-proof duct (f ield supply ) Unit: mm SPOT WELDING 4 POSITION SPOT WELDING 4 POSITION...
  • Page 89 8 . Supplement 3 . D imensions of Snow-proof V ents Ref erence diagram Q ’ ty Air-discharge Top side t 1.0 Unit: mm (32.5) 233.5 Air-discharge Right side t 1.0 Air-discharge Left side t 1.0 Snow-proof Top side 1 t 1.0 Snow-proof Rear side 1 t 1.0...
  • Page 90 8 . Supplement 2 Ref erence diagram f or A ir-discharge Right side (f ield supply ) Unit: mm 9 0° ø 3.3± 0.05 ø 6.5 2-M 4 FUNNEL EX TRUDED H OLE D TL FU NNEL EX TRU D ED HOL E(S= 1:1) (TH IS SURFACE 凹) (3 POSI TI ON) (1.7)
  • Page 91 8 . Supplement 4 Ref erence diagram f or Snow-proof Top side 1 (f ield supply ) Unit: mm (282.5) 2-ø 5.5 H OLE 5× 14.5 OV AL H OLE 15.9 6-ø 5.5 H OLE SEC A -A (S= 1:1) 282.5 303.5 Ref erence diagram f or Snow-proof Rear side 1 (f ield supply )
  • Page 92 8 . Supplement Ref erence diagram f or Snow-proof Right side 1 (f ield supply ) Unit: mm 9 0° ø 3.3± 0.05 ø D TL M 4 FU NNEL EX TRU D ED HOL E(S= 1:1) (5 POSI TI ON) 552.5 13.5 2-M 4 FUNNEL...
  • Page 93 8 . Supplement Ref erence diagram f or Snow-proof Top side 2 (f ield supply ) Unit: mm (69 0) 3-ø 5.5 H OLE 2-ø 5.5 H OLE 5× 27 OV AL H OLE 5× 15.6 OV AL H OLE 214.5 6-ø...
  • Page 94 8 . Supplement 10 Ref erence diagram f or Snow-proof Right side 2 (f ield supply ) Unit: mm 9 0° ø 3.3± 0.05 ø D TL M 4 FU NNEL EX TRU D ED HOL E(S= 1:1) (5 POSI TI ON) 552.5 13.5 2-M 4 FUNNEL...
  • Page 95 8 . Supplement 12 Ref erence diagram f or Pack ing (f ield supply ) Unit: mm EPT SEA L 10± 2 ADH ESIV E SEPARATOR 1-87...
  • Page 96: Capacity Table

    6.98 16.7 6.48 230V-240V 19.7 19.0 5.89 17.8 17.8 7.20 16.6 16.6 7.06 14.9 14.9 6.70 13.9 13.9 6.19 S-160PE1R5A 50Hz 1phase U-160PE2R8A 21.1 15.2 6.03 19.3 14.5 7.34 18.0 13.9 7.20 16.4 13.2 6.84 15.3 12.9 6.34 (400V-415V 22.5 11.4...
  • Page 97 10°C Source 14.6 3.70 16.4 4.15 17.5 4.43 19.0 5.48 19.4 5.54 20.0 5.57 21.0 5.61 21.2 5.62 230V-240V S-160PE1R5A 50Hz 1phase 13.6 3.99 15.4 4.45 16.5 4.72 18.0 5.78 18.4 5.84 19.0 5. 86 20.0 5.90 20.2 5.92 U-160PE2R8A...
  • Page 98 – MEMO – 1-90...
  • Page 99 2. TEST RUN 2. TEST RUN 2-1. Preparing for Test Run ..................... 2-2 Indoor Units (Type E1, E3) 2-2. Caution ........................2-3. Test Run Procedure ....................2-4. Items to Check Before the Test Run ............... 2-5. Test Run Using the Remote Controller ..............
  • Page 100: Preparing For Test Run

    2-1. Preparing for Test Run Before attempting to start the air conditioner, check the following: (1) All loose matter is removed from the cabinet especially steel filings, bits of wire, and clips. (2) The control wiring is correctly connected and all (Power must be turned ON at least electrical connections are tight.
  • Page 101: Items To Check Before The Test Run

    2-4. Items to Check Before the Test Run (1) Turn the remote power switch ON at least 12 hours in advance in order to energiz e the crankcase heater. (2) Fully open the closed valves on the liquid-tube and gas-tube sides. 2-5.
  • Page 102: Precautions

    2-6. Precautions Request that the customer be present when the test run is performed. At this time, explain the operation manual and have the customer perform the actual steps. Be sure to pass the manuals and warranty certificate to the customer. Check that the 230 –...
  • Page 104: System Control

    2-8. System Control System control refers to the link wiring connection for control of simultaneous-operation multi systems, group control, and main-sub remote controller control. 2-8-1. Basic wiring diagram Single type Be careful to avoid miswiring when connecting the wires. (Miswiring will damage the units.) (for 3-phase Outdoor unit) System address rotary switch Ground...
  • Page 105 2-8-2. Setting the Outdoor unit system addresses For basic wiring diagram (Set the system address: 1) Outdoor unit control PCB 6.5 – 9 HP LED 2 System address rotary switch (Set to “0” at time of shipment) LED 1 System address rotary switch SW 2 SW 1 System address...
  • Page 106 2-8 -3 . A utomatic address setting using the remote controller A uto A ddress Setting f rom the High-spec Wired Remote Controller (CZ-RTC5 A / B) K eep pressing the buttons simultaneously for 4 or more seconds. The “M aintenance func” screen appears on the LCD display. 20: 30 (TH U) Press the button to see each menu.
  • Page 107 Display During Auto Address Setting On the surface of outdoor unit control P.C. board * Do not short circuit the A.ADD pin again during auto address setting. LEDs 1 and 2 go out and address setting is interrupted. * When auto address setting is normally completed, both LEDs 1 and 2 go out. Blinks alternately In other cases, correct settings referring to the following table and perform auto address setting again.
  • Page 108 Check ing the indoor unit addresses Use the remote controller to check the indoor unit address. CZ-RTC5 A / B (High-spec wired remote controller) K eep pressing the buttons The “Simple settings” screen appears on the LCD display. simultaneously for 4 or more seconds. Select the “Unit no.”...
  • Page 109 2-8-4. Main-sub remote controller control Control using 2 remote controller switches Main-sub remote controller control refers to the use of 2 remote controllers to control 1 or multiple indoor units. (A maximum of 2 remote controllers can be connected.) Connecting 2 remote controllers to control 1 Indoor unit Remote controller Remote controller switch (main)
  • Page 110: Caution For Pump Down

    2-9. Caution for Pump Down Pump down means refrigerant gas in the system is returned to the outdoor unit. Pump down is used when the unit is to be moved, or before servicing the refrigerant circuit. This outdoor unit cannot collect more than the rated refrigerant amount as CAUTION shown by the nameplate on the back.
  • Page 111: Section 3 . El Ectri Ca L D A Ta

    3. ELECTRICAL DATA 3-1. Outdoor Units (Electric Wiring Diagram) ..............3-2 3-2. Indoor Units (Electric Wiring Diagram) ..............3-4 Ducted Type High Static Pressure Ducted Type...
  • Page 112 3-1. Outdoor Units 3-1. Outdoor Units Electric Wiring Diagram U-160PE2R8A Electric W iring Diag ram U-16 0 PE2 R8 A...
  • Page 113 Electric Wiring Diagram U-180PE2R8A / U-200PE2R8A / U-224PE2R8A...
  • Page 114 3-2. Indoor Units Ducted Type S-160PE1R5A Electric Wiring Diagram...
  • Page 115 H igh S tatic Pressure D ucted Type S -180PE3R 5 / S -200PE3R 5 Electric W iring D iagram...
  • Page 116 High Static Pressure D ucted Ty pe S-224PE3 R5 Electric Wiring D iagram...
  • Page 117 4. PROCESS AND FUNCTIONS 4-1. Control Functions ....................... 4 - 2 4-2. Outdoor Unit Control PCB (ACXA73-04770, ACXA73-04750) ......... 4 - 8 4-3. Outdoor Unit HIC Board (ACXA73-04760) ..............4-12 4-4. Indoor Unit Control PCB Switches and Functions ..........4-13...
  • Page 118: Control Functions

    4-1. Control Functions 1. Indoor Air Temperature Control The thermostat is switched on and off in accordance with T shown below. T= (Indoor air temperature) - (Temperature set with the remote controller) In the body thermostat mode Indoor air temperature = (Body sensor) - (Shift temperature *) (setting at factory shipment) In the remote controller thermostat mode Indoor air temperature = (Remote controller sensor) * Shift Temperature...
  • Page 119 1) Indoor Air Temperature Control By the control method, not only the thermostat is switched on and off, as explained section “1. Indoor Air Temperature Control ", but also the frequency of the compressor's inverter is controlled in accordance with T and fluctuations in indoor air temperature.
  • Page 120 4) Condensation Temperature Control (cooling) This system control is performed to limit the inverter frequency in order to restrict high pressure’ s abnormal increase and high-load operating prevention in the cooling mode. In accordance with the temperature of the outdoor heat exchanger temperature sensors (C1, C2), such controls are performed as to halting the operations of the indoor unit, decreasing the inverter frequency and restricting its increase, etc.
  • Page 121 6 ) Cooling Freez e Prev ention Control The following control is performed during cooling operations (including dry mode operation), in accordance with whichever of the indoor heat exchanger temperatures (E1 or E2) is lower. (See the chart below.) (a) Frequency will not be decreased less than 6 minutes after thermostat ON. (b) The threshold value is increased in accordance with the indoor load (differences of temperature).
  • Page 122 8) Defrosting Control This control function removes frost that has adhered to the outdoor heat exchanger during the heating operation. The control is performed to prevent the deterioration of the heating capabilities attributed to the adherence of frost, and to prevent the crack or crush of pipes attributed to the accretion of ice. The following control is performed in accordance with the ambient temperature and the outdoor heat exchanger temperature sensor (C1).
  • Page 123 Ending Defrosting Defrosting operations are ended when the following conditions are satisfied. Ending defrosting conditions When the temperature of the outdoor heat exchanger temperature sensor (C1) is 10°C or higher. When the temperature of the outdoor heat exchanger temperature sensor (C1) is 6°C or higher for consecutive 60 seconds.
  • Page 124: Outdoor Unit Control Pcb (Acxa73-04770, Acxa73-04750)

    4-2 . Outdoor Unit Control PCB U-16 0 PE2 R8 A, U-18 0 PE2 R8 A ( ACX A7 3-0 47 7 0 ) LED1 LED2 TEST MODE PUMPDOWN A.ADD CH K STOP...
  • Page 125 U-2 0 0 PE2 R8 A, U-2 2 4PE2 R8 A ( ACX A7 3-0 47 5 0 ) LED1 LED2 TEST MODE PUMPDOWN CH K STOP A.ADD 4-9 4-9...
  • Page 126: Outdoor U Nit Control Pcb (A Cx A 7 3 -0 47 7 0 , A Cx A 7 3 -0 47 5 0 )

    Outdoor U nit Control PCB (A CX A 7 3 -0 47 7 0 , A CX A 7 3 -0 47 5 0 ) Explanation of Functions A. ADD pin (2P, Black) Auto address setting pin Short-circuit this pin for 1 second or longer to automatically set the addresses at the indoor units that are connected to that outdoor unit and are within the same system.
  • Page 127 Table 4-1. Method of System Address Setting [SW2 (rotary, yellow), SW1 (2P DIP switch, black)] Outdoor system SW2 setting SW1 setting address No. (system address switch) 1P (10s-digit place) 2P (20s-digit place) 1 system only System controller Outdoor Outdoor Outdoor Outdoor Indoor Indoor...
  • Page 128: Outdoor U Nit Hi C Board (A Cx A 7 3 -0 47 6 0 )

    4-3. Outdoor Unit HIC Board U-160PE2R8A, U-180PE2R8A, U-200PE2R8A, U-224PE2R8A (ACXA73-04760) 4-12...
  • Page 129: I Ndoor U Nit Control Pcb Switches And Functions

    4-4. I ndoor U nit Control PCB Switches and Functions [ I ndoor unit control PCB] T10 (CN0 6 1): 6 P plug (Y EL ) / Used for remote control operation. (Refer to the Remote Control Section.) Control items: (1) Start/stop input (2) Remote controller prohibit input (3) Start signal output (4) Alarm signal output...
  • Page 130 Indoor U nit C ontrol PC B C 3937-840-1Y : S -160PE1R 5A PO W ER LED EEPR O M F AN D R IVE EX CT O PTIO N CHK Pin D ISP J P 001 A C X A 73-1875 : S -180PE3R 5, S -200PE3R 5, S -224PE3R 5 PO W ER LED (D 002) EX CT (CN 073) EEPR O M (IC010)
  • Page 131 5. TROUBLE DIAGNOSIS 5-1. Contents of Remote Controller Switch Alarm Display .......... 5-2 5-2. Outdoor Unit Control Panel LED Display ..............5-4 5-3. PAC System Alarm Codes ..................5-5 5-4. Inspection of Parts (Outdoor Unit) ................5-32 5-5. Symptom: Thermostat in OFF continues or cycles OFF & ON too frequently ..5-33 5-6.
  • Page 132: Contents Of Remote Controller Switch Alarm Display

    5-1. Contents of Remote Controller Switch Alarm Display Blinking: OFF: Wireless remote controller receiver display Wired remote Possible cause of malfunction control display Faulty remote controller Failure in receiving serial signal from remote controller's Disconnection/Contact failure of remote controller wiring indoor unit CHK(check) pins on the indoor unit control PCB are short circuited In the case of non-group control:...
  • Page 133 Blinking: OFF: Wireless remote controller Wired receiver display remote Possible cause of malfunction control display Faulty wiring connections of (ceiling) indoor unit panel Indoor unit fan motor locked Indoor unit fan motor trouble Indoor unit fan motor layer short (AC fan) Contact failure in thermostat protector circuit Faulty drain pump Timer and standby...
  • Page 134: Outdoor Unit Control Panel Led Display

    5-2. Outdoor Unit Control Panel LED Display : ON : Blinking : OFF ) LED1 LED2 Display meaning After the power is turned ON (and automatic address setting is not in progress), no communica- tion with the indoor units in that system is possible. (Both ON) After power is turned ON (and automatic address setting is not in progress), 1 or more indoor units are confirmed in that system;...
  • Page 135: Pac System Alarm Codes

    5-3. PAC System Alarm Codes Alarms for outdoor units Alarm Alarm Meaning Code Remote Controller Reception Error Remote Controller Transmission Error Error in Indoor Unit Receiving Signal from Remote Controller (central) Error in Indoor Unit Receiving Signal from the Outdoor Unit Error in Indoor Unit Transmitting Signal to the Outdoor Unit Outdoor Unit Failed to Receive Serial Communication Signals from Indoor Unit Duplicate Indoor Unit Address Settings Error...
  • Page 136 Symptoms and Parts to Inspect Remote Alarm Eliminating controller Judgement conditions Judgement and correction contents condition of alarm alarm display Abnormal discharge Stops when temp. exceeds Recovery at restart 1. Check refrigerant cycle (gas temperature error leak). • Discharge temp. Alarm output on 5 pre-trips 2.Trouble with electronic detected at or...
  • Page 137 Check Prior to Auto Address Setting * If an outdoor unit displays an alarm, conduct this process after diagnosing the problem. 1 Auto Address Is the power of the indoor unit(s) and outdoor unit(s) on? Power on. Indoor/ Has the wiring of the indoor/outdoor control line been completed? outdoor Is it all connected? Connect the wiring.
  • Page 138 Mini VRF SYSTEM Trouble Diagnosis 4. Mini VRF System Alarm Codes E04 Error in Indoor Unit Receiving Signal from the Outdoor unit Error Detection Method When there is no communication within a 3-minute period from the outdoor unit. Or, judged an error when no reply comes from the outdoor unit.
  • Page 139 E0 6 Outdoor U nit Failed to Receiv e Serial Communication Signals f rom I ndoor U nit (When indoor unit(s) are connected) Error D etection M ethod It is j udged an error when there is no transmission (reply) from the indoor unit to the outdoor unit for a period of three minutes. The indoor unit is not turned on.
  • Page 140 E15 A utomatic A ddress A larm (The total capacity of indoor units is too low.) Error D etection M ethod Connecting indoor unit It is j udged an error the total capacity of indoor units replied by communication is lower than that of outdoor unit. The total capacity of indoor units is lower than that of outdoor unit.
  • Page 141 E16 Automatic Address Alarm (The total capacity of indoor units is too high.) Error Detection Method It is judged an error the total capacity of indoor units is too high or the total number of indoor units is too many. The total capacity of indoor units is too high.
  • Page 142 F06 Inlet Temperature Sensor (C1) in Heat Exchanger Trouble Error Detection Method In case of open or short • Error Diagnosis 1 Sensor Is the connector properly connected to PCB? Trouble Reconnect & check. Replace sensor. Is the resistor between the sockets infinity or 0 ? 2 Control Outdoor unit control PCB failure Replace PCB with a new one.
  • Page 143 F12 Compressor inlet Suction Temperature Sensor (TS) Trouble Error Detection Method It is judged an error when open circuit or short circuit. Error Diagnosis 1 Sensor Sensor connector is connected to PC board properly. Reconnect and check. Replace sensor. Resistance between sockets is infinity or 0 ohm. 2 Outdoor control Replace PC board because of outdoor control PC board failure.
  • Page 144 H01 Primary (input) Overcurrent Detected Error Detection Method Primary current effective value detected overcurrent (trip current value). Trip current value HP = horse power 3-phase model 7 HP 8 HP 9 HP Heating 23.0A 23.0A 23.0A Cooling 21.5A 21.5A 21.5A Error Diagnosis 1 Power Check power supply.
  • Page 145 H03 Primary Current CT Sensor (current sensor) Failure Error Detection Method It is judged an error based on the criteria listed below. If 18A or greater is detected when the compressor is stopped (alarm triggered even if the connector is unplugged). If no current is detected even though a compressor is running.
  • Page 146 H31 HIC Trouble Error Detection Method It is judged an error if the computer detects an error signal from the HIC. An error signal is issued by the HIC if abnormal heat occurs inside the HIC or if there is an overcurrent. However, it is judged an error in the same way if the signal line from the HIC is not connected properly or opened.
  • Page 147 Tester terminals HIC- HIC+ Resistance value (ohm) 1 k to 10 k 1 k to 10 k 1 k to 10 k 5 k to 20 k 20 k to 20 k to 20 k to 20 k to Tester terminals Resistance value (ohm) 20 k to 20 k to...
  • Page 148 L04 Outdoor Unit Address Duplication Error Detection Method It is judged an error when the identical self-address communication on the indoor and outdoor wirings is received over 5 times within 3 minutes. Error Diagnosis 1 System Are other outdoor units using a duplicate setting? address Installation When units are networked, first set the system address for each outdoor unit in the order...
  • Page 149 L18 4-way Valve Operation Failure Error Detection Method It is judged an error when during heating operation (Comp. ON), the highest detected temperature at an outdoor unit heat exchanger (C1) was 20°C or more above the outdoor air temperature (Air Temp.) continuously for 5 minutes or longer.
  • Page 150 P04 High Pressure Trouble Error Detection Method It is judged an error if the internal circuit of the high pressure switch is dead. The electronic circuitry of the high pressure switch is cut off if the pressure at the pressure sensor port of the high pressure switch reaches 3.80 MPa.
  • Page 151 3 Problem Prevent air short The intake temperature (ambient temperature) of the indoor unit is around the circuit. above 36°C. heat exchanger Clean the filter. The filter of the indoor unit is clogged. Replace the indoor fan (motor). The fan of the indoor unit is broken or the fan motor is faulty. 4 Blockage Is the outdoor unit’s electronic control valve operating correctly? in the...
  • Page 152 Mini VRF SYSTEM Trouble Diagnosis 4. Mini VRF System Alarm Codes P05 AC Power Supply Trouble Error Detection Method Instantaneous blackout Zero-cross (waveform input of power supply) error DC voltage charge failure Error Diagnosis Note : The work involved in diagnosing each of the items is extremely dangerous, so turn the power off at the breaker before performing the tests.
  • Page 153 P13 Alarm Valve Open Error Detection Method Detection is performed only in the test run. When once detected or the test run finished without any error, the second detection will not be done. In case of forgetting to open a valve, P04 (high-pressure switch operational alarm) is occasionally preceded due to the following conditions.
  • Page 154 P15 Insufficient Gas Level Detected Abnormal Detection Method Alarm occurs in the following cases: Compressor's current value shows lower than a certain value. Compressor's discharge temperature exceeds 95°C. Electronic expansion valve is fully opened. The difference between indoor unit heat exchanger temperature and intake temperature is less than 4K. Error Diagnosis 1 Adjustment Recharge with...
  • Page 155 P16 Compressor Overcurrent Trouble Meaning of Alarm Secondary current effective value detected the overcurrent (trip current value). 3-phase model (7HP – 9HP) : Trip current = 24.3 A Secondary current instantly detected overcurrent (trip current value). 3-phase model (7HP – 9HP) : Trip current = 50.0 A Check of content 0 Multiple Replaced the compressor (added oil, if it was necessary)
  • Page 156 Mini VRF SYSTEM Trouble Diagnosis 4. Mini VRF System Alarm Codes 4 Check the Take measures. Outdoor air intake temperature is high. situation Correct May be caused by poor outdoor unit air flow (dirty or clogged heat exchanger, blocked discharge port, etc.) Prevent air short Air short circuit has occurred.
  • Page 157 Mini VRF SYSTEM Trouble Diagnosis 4. Mini VRF System Alarm Codes 9 Check the See what happens. Replace the HIC PC board and operate the unit. (Apply putty and HIC PC screws must not be loose) Does it operate normally? boards 10-1 10 Check the...
  • Page 158 Mini VRF SYSTEM Trouble Diagnosis 4. Mini VRF System Alarm Codes P22 Outdoor Unit Fan Motor Trouble Error Detection Method It is judged an error when the outdoor fan motor’s rotating signal cannot be detected normally. Error Diagnosis 1 Wiring Are the connectors “CN-FM_UP”...
  • Page 159 P29 Lack of INV compressor wiring, INV compressor actuation failure (including locked), DCCT failure Error Detection Method Abnormal current is detected at DCCT before start-up. Start-up failed during overcurrent and/or step-out detected. Open-wire of compressor and/or backspin detected. Secondary current is not detected during INV compressor is running. Error Diagnosis Correct wiring 1 Wiring...
  • Page 160 ■ Outdoor Unit Control HIC PCB ACXA73-04760 : (U-160PE2R8A, U-180PE2R8A, U-200PE2R8A, U-224PE2R8A) (3-phase outdoor unit HIC PC board) 5-30...
  • Page 161 Mini VRF SYSTEM Trouble Diagnosis 4. Mini VRF System Alarm Codes P31 Group Control Error Error Detection Method Other indoor unit alarms within the group. 1 Other indoor Survey the indoor unit that alarms other than “P31” in the indoor unit group and specify the unit causes of failure.
  • Page 162: Inspection Of Parts (Outdoor Unit)

    Mini VRF SYSTEM Trouble Diagnosis 5-4. Inspection of Parts (Outdoor Unit) 5. Inspection of Parts (Outdoor Unit) (1) Electronic control valve (MOV1) MOV1: Measure the voltage between plug pin 5 and pins 1 through 4 at the CN-MOV1 connector (5P, white) on the outdoor unit control PCB.
  • Page 163: Sy Mptom: Thermostat In Off Continues Or Cy Cles Off & On Too F Req Uently

    Mini VRF SYSTEM 6. Symptom: Thermostat in OFF continues or Trouble Diagnosis 5-5. Symptom: Thermostat in OFF continues or cycles OFF & ON too frequently cycles OFF & ON too frequently How to detect abnormality Abnormality does not occur. Protective function can be checked when the outdoor maintenance remote controller is connected.
  • Page 164: Sensor Temperature D Isplay Function (Displayed Regardless Of Operation And Stop)

    5 -6 . Sensor Temperature D isplay Function (Displayed regardless of operation and stop) The procedure below displays the sensor temperatures from the remote controller, indoor unit, and outdoor unit on the remote controller. (1) Press and hold the buttons simultaneously for 4 seconds or longer.
  • Page 165: Table Of Thermistor Characteristics

    5-7. Table of Thermistor Characteristics (1) Outdoor Air Temp. (TO) Sensor, Intake Temp. (TS) Sensor, Heat Exchanger Temp. (C1) Sensor, Heat Exchanger Temp. (C2) Sensor -20 -15 -10 Temperature ( C) Temperature ( C) (2) Discharge Temp. (TD) Sensor 90 100 110 Temperature ( C) 5-35...
  • Page 166: How To Remove The Compressor

    5-8. How to Remove the Compressor Pay careful attention to prevent water or foreign objects from entering into the refrigerant tubing when removing or installing the compressor. Removing 1.After collecting the refrigerant in the system, replace nitrogen gas from the service port of the gas tubing valve. 2.Remove the sound absorbing material protecting the compressor.
  • Page 167: How To Remove The Electrical Component Box

    5-9 How to Remove the Electrical Component Box Removing 1.Remove the front panel and inspection panel from the outdoor unit. 2.Remove all local wires connected to the electrical component box. 3.Remove the wires (temperature sensor, coils of every sort of valve, pressure switch, fan motor and wires for connecting compressor) connected to the electrical component box in the unit.
  • Page 168: Symptom: Thermostat In Off Continues Or Cycles Off & On Too Frequently

    Mini VRF SYSTEM 6. Symptom: Thermostat in OFF continues or Trouble Diagnosis cycles OFF & ON too frequently How to detect abnormality Abnormality does not occur. Protective function can be checked when the outdoor maintenance remote controller is connected. Error Diagnosis Adjust setting Indoor control Setting temperature reaches the level set ON thermostat.
  • Page 169 6. OUTDOOR UNIT MAINTENANCE REMOTE CONTROLLER In the case of CZ-RTC4 6-1. Overview ........................6-2 6-2. Functions ........................6-2 6-3. Normal Display Operations and Functions ............. 6-3 6-4. Monitoring Operations: Display of Indoor Unit and Outdoor Unit Sensor Temperatures ......................6-8 6-5.
  • Page 170: Overview

    6-1. Overview What is the outdoor unit maintenance remote controller? Beginning with the DC-INV series of outdoor units, nonvolatile memory (EEPROM) is used in the outdoor unit PCB. In this way, the setting switches that were located on earlier PCBs have been converted to EEPROM data. This remote controller is an outdoor unit maintenance tool that is used to make and change the EEPROM set- tings.
  • Page 171: Normal Display Operations And Functions

    6-3. Normal Display Operations and Functions Normal display functions • Connect the special service checker wiring to the outdoor unit PCB. The connection is shown in the figure below. When connecting the special service Outdoor unit PCB checker wiring to the remote controller (3P, BLU) CZ-RTC4, cut out the wire as shown in the Special service...
  • Page 172 All units start/stop (Fig. 6-1) <Operation> (Start/Stop operation) button can be used to start and stop all the indoor units. • The LED illuminates if any indoor units is operating. • The LED blinks if an alarm at any of the operating indoor units occurs.
  • Page 173 n Display (functions) • Use the temperature setting buttons to change the item code. (1) Item code (2) Item Remarks Alarm code display Outdoor unit alarm No. of connected indoor units Quantity Unit Nos. of connected indoor unit 7-segment display Operating status of indoor unit 7-segment display Thermostat ON status of indoor unit...
  • Page 174 (3) XX-YY R.C. Locations where (1), (2), and (3) are displayed as Displays the outdoor unit sub-bus address which is shown in Fig. 6-4. currently selected. XX = Outdoor system address on main bus line (1 – 30) YY = Outdoor unit sub-bus address (1 – 8) “1”...
  • Page 175 n 7-segment, 4-digit display for remote controller timer display The connected unit Nos. are displayed as shown below, using the 7-segment 4-digit ( ) display and the colon.  Display for unit Nos. 1 – 20 Not lit Not lit Not lit Not lit Meaning of display colon...
  • Page 176: Monitoring Operations: Display Of Indoor Unit And Outdoor Unit Sensor Temperatures

    6-4. Monitoring Operations: Display of Indoor Unit and Outdoor Unit Sensor Temperatures <Operating procedure> (1) Press and hold the (Check) button and buttons simultaneously for 4 seconds or longer to engage temperature monitor mode. During temperature monitoring, is illuminates. (The display and operations are the same as for monitor mode using the indoor unit remote controller.) (2) Press the...
  • Page 177 D isplay of unit No. 1 (main unit) Item code M eaning of Code Indoor unit data Indoor unit intake temp. Indoor unit heat exchanger temp. (E1) Indoor unit heat exchanger temp. (E2) – – – – Outdoor unit data Discharge temp.
  • Page 178: Monitoring The Outdoor Unit Alarm History: Display Of Outdoor Unit Alarm History

    6-5. Monitoring the Outdoor Unit Alarm History: Display of Outdoor Unit Alarm History * Displays outdoor unit alarms only. Does not display indoor unit alarms. * Check the indoor unit alarm histories separately using the indoor unit remote controllers or other control device. <Operating procedure>...
  • Page 179: Settings Modes: Setting The Outdoor Unit Eeprom

    6-6. Settings Modes: Setting the Outdoor Unit EEPROM 2WAY SYSTEM  Setting mode 1 6. Mode Settings Outdoor Unit Maintenance Remote Controller <Operating procedure> Press and hold the (Check) button and Display of fi rst 3 digits (Ventilation) button simultaneously for 4 seconds or longer.
  • Page 180 Never use the DN code unlisted in the following table. (P) : Factory preset mode Item Setting No. 1= Silent mode 1 (P) Outdoor fan silent mode 2= Silent mode 2,,,,, 3= Silent mode 3 Capacity matching ignored 0= Invalid (P) 1= V alid 0= Invalid 1= stop for 2 hours and drive for 20 minutes constantly...
  • Page 181 7. REMOTE CONTROLLER FUNCTIONS SECTION 7-1. Simple Settings Function .................... 7-2 7-2. List of Simple Setting Items ..................7-3 7-3. Detailed Settings Function ..................7-4 7-4. List of Detailed Setting Items ..................7-5 7-5. Simple Setting Items....................7-8 7-6. Detailed Setting Items ....................7-10 7-7.
  • Page 182: Remote Controller Functions Section

    Optional Controller 4. Simple Settings Function Remote Controller Functions 7-1. Simple Settings Function This allows the filter lifetime, operating mode priority change, central control address, and other settings to be made for an individual or group-control indoor unit to which the remote controller used for simple settings is connected.
  • Page 183: List Of Simple Setting Items

    7-2. List of Simple Setting Items Setting data Item code Item Description 0000 Not displayed 0001 150 hours Filter sign ON time 0002 2,500 hours (filter life time) 0003 5,000 hours 0004 10,000 hours 0005 Use the filter clogging sensor. 0000 Standard (setting at time of shipping) Degree of filter fouling Highly fouled...
  • Page 184: Detailed Settings Function

    Optional Controller 5. Detailed Settings Function Remote Controller Functions 7-3. Detailed Settings Function This allows the system address, indoor unit address, and other settings to be made for the individual or group-control indoor unit to which the remote controller used for detailed settings is connected. When detailed settings mode is engaged, operation stops at the individual or group-control indoor unit where the remote controller used for detailed settings is connected.
  • Page 185: List Of Detailed Setting Items

    7 -4. L ist of D etailed Setting I tems Setting data I tem I tem code D escription D escription D escription 0000 0001 0002 Ducted (E1) 0006 H igh Static Pressure 0003 0005 Type Ducted (E3) 0007 0008 0010 0011 0001...
  • Page 186 Setting data Item code Item Description 0000 5 minutes Forced thermostat ON (1B) 0001 4 minutes – 10°C – 010 – 9 °C – 009 Cooling discharge – 8°C – 008 temperature shift 0010 10°C – 10°C – 010 – 9 °C –...
  • Page 187 Setting data Item code Item Description None 0000 Ventilation fan operation 0001 Ventilation fan operated by remote controller. Wired remote controller 0000 Not used. (Body sensor is used.) Remote controller sensor is used. 0001 sensor Normal (displayed) 0000 “Operation change control in progress”...
  • Page 188: Simple Setting Items

    7-5. Simple Setting Items Item code Item Description Filter sign ON time setting Changes the indoor unit filter lifetime when a high-performance filter or (filter lifetime) other optional product is installed. Reduces the filter sign ON time to 1/2 of the standard time (setting at the Degree of filter fouling time of shipping) for cases when filter fouling is more severe than normal.
  • Page 189 When the operating mode at the priority remote controller is changed, the operating modes of other remote controllers change as shown below. Mode change at priority remote controller Operating modes at other remote controllers Current mode New mode Current mode New mode Cooling or dry Heating...
  • Page 190: Detailed Setting Items

    7-6. Detailed Setting Items Item code Item Description Unit type Set when the indoor unit EEPROM memory is replaced during servicing. Indoor unit capacity System (outdoor unit) These are not set at the time of shipping from the factory. address These must be set after installation if automatic address setting is not Indoor unit address performed.
  • Page 191 Item code Item Description 1F (Upper limit) Cooling 20 (Lower limit) This setting changes the temperature range (upper limit and lower 21 (Upper limit) Change to the Heating limit) which is set from the remote controller or central control device. 22 (Lower limit) remote control The set upper limit must be greater than or equal to the lower limit.
  • Page 192 (Continued from previous page) Item code Item Description Heat exchanger The heat exchanger temperature control point for prevention of cold temperature for cold air air discharge during heating operation can be changed. discharge The indoor unit PCB optional output for the fan can be switched Fan output switching according to the purpose of use.
  • Page 193: Remote Controller Servicing Functions

    Optional Controller 1. Remote Controller Servicing Functions Remote Controller Functions 7-7. Remote Controller Servicing Functions The remote controller includes a number of servicing functions. Use these as needed for test runs and inspections. CZ-RTC4 Fig. 7-3 List of Servicing Functions Functions D escription Button operation...
  • Page 194: Test Run Function

    2. Test Run Function Remote Controller Functions 7-8. Test Run Function Operates the unit with the thermostat forced ON. Press and hold the button for 4 seconds or longer. ° “ ” appears on the remote controller LCD ° display (Fig. 7-4). Press the button to start the test run.
  • Page 195 Sensor Temperature Display Function (displayed regardless of whether unit is operating or stopped) The procedure below display the sensor temperatures from the remote controller, inddor unit, and outdoor unit on the remote controller. ° Press and hold the buttons ° simultaneously for 4 seconds or longer.
  • Page 196 – MEMO – 7-16...
  • Page 197 8. HOW TO INSTALL THE WIRELESS REMOTE CONTROLLER RECEIVER 8. HOW TO INSTALL THE WIRELESS REMOTE CONTROLLER RECEIVER Important Safety Instructions ..................8-2 Optional Controller (Remote Controller) ................ 8-1. Names and Functions ....................8-2. Installing Batteries ....................8-5 8-3. Setting the Current Time ..................8-4.
  • Page 198: Important Safety Instructions

    Important Safety Instructions WARNING Installation Precautions Do not install yourself Installation should always be performed by your dealer or a professional service provider. Electric shock or fire may result if an inexperienced person performs any installation or wiring procedures incorrectly. Use only specified air conditioners Always use only air conditions specified by the dealer.
  • Page 199: Optional Controller (Remote Controller)

    2. Wireless Remote Controller Optional Controller (Remote Controller) Wireless Remote Controller CZ-RWSK 2 One remote controller can control a group of up to eight indoor units. 8 -1. Names and Functions REM OTE CONTROL L ER Displays the operation status. 15 .
  • Page 200 RECEIVER CZ-RWSC3 1. Receiver Receives the signal sent from the remote controller. 2. Emergency Indicator lamps operation When an error occurs, one of the button lamps flashes. When an indicator lamp is flashing, refer to “8-13. Before Requesting Service”. OPERATION lamp Lights up when the unit is operating.
  • Page 201: Installing Batteries

    8-2. Installing Batteries 1. Remove the cover. 2. Insert two LR03 size batteries. Put the batteries in with the polarity [+/–] as shown in the figure. 3. Gently insert one end of an unfolded paper clip (or a similar object that can fit) into the Reset hole and press the Reset button inside the hole, then put the cover back on.
  • Page 202: Operation

    8-4. Operation , Dry , Cool , Fan Auto , Heat Models that only provide the cooling function cannot operate in the auto or heating modes. Power: Turn on the power of the indoor unit at least 14 hours before operation. 1.
  • Page 203: Timer Operation

    8-5. Timer Operation When setting the timer, make sure the current time on the remote controller is accurate. The timer’s clock can only be set when the display of the remote controller is ON. After setting the timer, put the remote controller in a place where its signal will reach the receiver of the indoor unit.
  • Page 204: Adjusting The Wind Direction

    8-6. Adjusting the Wind Direction CZ-RWSC3 The available functions differ depending on the indoor unit being used. The wind direction cannot be set via remote controller for any models other than those noted below. For more information, please refer to the Operating Instructions that came with your indoor unit.
  • Page 205: Using The Remote Controller

    8-8. Using the Remote Controller Point the transmitter of the remote controller at the receiver. When the signal is received correctly it will beep once. (It beeps twice only when the unit starts operating.) The signal can be received at a distance of about 6 meters. This distance should be used only as a guide. It depends on battery strength.
  • Page 206 C ont r ol of 2 W A Y SYSTEM 2. Wireless Remote Controller M atching up A ddresses Setting Remote Controller A ddresses 1. I f y ou press at the same time, “ ” will blink . 2. While holding down, ev ery time y ou press , it cy cles f rom A L L 3 …...
  • Page 207: Emergency Operation

    C ont r ol of 2 W A Y SYSTEM 2. Wireless Remote Controller 8 -11. Emergency Operation Use [ Emergency Operation] in the following situations when there is an urgent need. When the remote controller’ s batteries have failed. When the remote controller is broken.
  • Page 208: Miscellaneous Settings

    8 -12. M iscellaneous Settings A variety of changes can be made to settings, depending on the indoor unit being used. Operation mode indicator, time display (24 hour, A M / PM ), Heat M ax Temp (These settings are saved in nonvolatile memory in the remote controller, so even when its batteries are changed, the settings do not have to be made again.) First check the display of the remote controller when the unit is stopped and then make any desired settings.
  • Page 209: Before Requesting Service

    2. Wireless Remote Controller 8 -13 . Bef ore Req uesting Serv ice Before requesting service, please check the followings. Solution The power to the indoor unit is not ON. M ake sure the power to the indoor unit is ON. The unit doesn’...
  • Page 210: How To Install The Wireless Remote Controller Receiver

    How to Install the Wireless Remote Controller Receiver 8-14. Common to All Models 1. Warnings about Installation of Receivers The wireless remote controller uses a very weak infrared light for its signal, which can result in the signal not being received because of the following influences, so take care in where the unit is installed.
  • Page 211: Rwsc3

    C ont r ol of 2 W A Y SYSTEM 2. Wireless Remote Controller CZ-RWSC3 ADDRESS 1 ADDRESS 2 ADDRESS 3 SUB/M AIN 1 2 3 4 Front side Rear side 8-15...
  • Page 212 C ont r ol of 2 W A Y SYSTEM 2. Wireless Remote Controller 8 -15 . CZ-RWSC3 Installation Instructions Dimensions Wireless Receiver for ALL Part Names Unit: mm (1) Light receiving section 9 .4 Receives signals. (2) Emergency operation button Starts/Stops emergency operation.
  • Page 213 C ont r ol of 2 W A Y SYSTEM 2. Wireless Remote Controller 2. I nstalling the Receiv er Remov e the bottom case. A ttention M ounting the bottom case  Tighten the screws securely until the screw heads touch the bottom case.
  • Page 214 C ont r ol of 2 W A Y SYSTEM 2. Wireless Remote Controller 3 . Wiring the Receiv er Wiring for the receiver Wiring diagram Ty pe of wiring Receiver Indoor unit Use cables of 0.5 to 1.25 mm Total wire length: 400 m or less RC wiring (fi eld supply) (The wire length between indoor...
  • Page 215 C ont r ol of 2 W A Y SYSTEM 2. Wireless Remote Controller 4. Setting A ddress Switches M ain/ Sub setting A ddress setting Remov e the top case of the receiv er f or setting. M ain/Sub setting ...
  • Page 216 8-16. Common to All Models 1. The Self-Diagnosis Function Display and What is Detected Alarm Display in the table below indicates the content of alarms that are displayed when a wired remote controller is connected. For information on how to deal with the alarms, refer to the Mounting Instructions for the indoor unit or to Test Run or servicing materials.
  • Page 217 3. Setting Up Remote Controller Functions The functions of the wireless remote controller can be set on site. (These settings are saved in nonvolatile memory in the remote controller, so even when its batteries are changed, the settings do not revert to the defaults.) NOTE The operation of the air conditioner can be impacted, depending on the settings made, so only service personnel should make the settings.
  • Page 218 201801...