5. Enter operation ready status (normal stop status)
Press
button to enter operation ready status.
After that, normal operation can be performed.
nd
・For the 2
nd
"P158: The 2
Number", "P160: The 2
and "P161: The 2
●When tuning result is beyond specific range
Sometimes, special-purpose motors such as high-speed motor
and high-slip motor etc. cannot be tuned correctly. In case that
improper tuning is performed, "tEr1" and "tEr2" will be displayed
and fault trip will occur. Just press STOP SW button to reset.
P133
Voltage Compensation Constant
During vector control or when auto torque boost is performed through V/F
control, necessary voltage compensation constants should be set.
Setting value (V)
The setting value of voltage compensation constant can be calculated by the
following formula.
Setting value = R x I R: including one-phase resistance of wiring
motor, related parameters are as follows.
Motor Capacity", "P159: The 2
nd
Voltage Compensation Constant"
nd
Slip Compensation Frequency".
0.01 to 99.99 (increment =
0.01)
(1/2 of measured resistance between motor
terminals)
I: Equivalent current (Equivalet to rated current of
inverter corresponding to motor with same
capacity)
Appendix Function Parameter List
nd
Motor Pole
251