11.3 Common Specifications
Items
Frequency range
Frequency display
Output
Frequency
Frequency accuracy
Frequency resolution
Inverter control mode
Carrier frequency
Start/Stop
Forward/Reverse run
Operation
JOG operation
Stop mode
Reset function
Start frequency
Stop frequency
Specifications
0.5 to 400 Hz
Digital display
Analog setting: within ±0.5% of maximum setting
frequency (25°C±10°C)
Digital setting: within ±0.01% of maximum setting
frequency (-10°C to +50°C)
Digital setting: 0.1 Hz
Analog setting: 0.1 Hz (in 50/60 Hz mode)
High carrier frequency sinusoidal PWM control
(V/F control or simple vector control is available.)
•
V/F control setting: 7 options can be selected
(adjustable from 0.8 to 10 kHz).
•
Simple vector control setting: 4 options can be
selected (adjustable from 2.5 to 10 kHz).
(0.8, 1.1, 1.6, 2.5, 5.0, 7.5, 10.0 kHz)
•
Operation panel buttons
•
1a contact signal and 3-wire input (1a and 1b
contact signals) can be selected.
•
RS485 communication
•
Wait time (0.1 to 100 s) can be set.
•
Operation panel buttons
•
1a contact signal (reverse run can be disabled.)
•
RS485 communication
Operation frequency: adjustable from 0.5 to 400 Hz
Acceleration/deceleration time: adjustable from
0.04 to 3600 s
Ramp-to-stop / coast-to-stop (switchable)
Stop signal reset/external reset/panel reset
(optional) / power supply reset
Adjustable from 0.5 to 60 Hz
Adjustable from 0.5 to 60 Hz
11. Specifications
133