Panasonic VF200 Instruction Manual page 144

Table of Contents

Advertisement

Items
Details of abnormality
Current limit
Protection
Trip (stop)
Stall prevention function
Ambient temperature and
humidity
Storage temperature and
humidity
Environment
Vibration
Altitude
Location
Enclosure
Cooling method
Note 1) It is -10 to +40°C when multiple inverters are installed side-by-side.
Specifications
Specific symbol is indicated when the protection
function is activated (the latest four abnormalities
are stored.)
Current limit can be set within 1 to 200% of rated
output current.
Instantaneous overcurrent (SC1-6) and abnormal
temperature (OH)
Overcurrent (OC1-3), overload and electronic
thermal relay (OL), undervoltage (LU), overvoltage
(OU1-3), cooling fan fault (FAn), external fault (AU),
operation fault (OP) and CPU fault (CPU)
Overcurrent and overvoltage stall prevention
-10 to +50°C (Note 1) (without freezing) and below
90%RH (without condensation)
-25 to +65°C and below 95%RH
2
5.9 m/s
(0.6G) or lower
1000 m or lower
Indoor areas free of corrosive gases, flammable
gases, oil mist or dust
IP20 cabinet-mousssnted
200 V 0.2 to 0.75 kW: self-cooling; 1.5 to 2.2 kW:
air-cooling
400 V 0.75 kW: self-cooling; 1.5 to 15 kW:
air-cooling
11. Specifications
137