Pid Control Switching Function - Panasonic VF200 Instruction Manual

Table of Contents

Advertisement

Appendix Function Parameter List

■PID Control Switching Function

Signal input terminal for cancelling PID control through external control can
be set. When the signal input is turned ON, the inverter switches from "PID
control" to the the command set with parameter P004.
nd
The function is valid when parameter "P124: The 2
Analog Input Function
Select" is set to "1 to 3".
・When the signal input is OFF: PID control or control based on auxillary
frequency signal
・When the signal input is ON: command set with parameter P004
< Example > When SW1 (parameter P036 = 9) is set to frequency switching
Related paremeters: P004, P124, P101 to P104
181