Cooling Fan On-Off Control Select; Input Terminal Filter - Panasonic VF200 Instruction Manual

Table of Contents

Advertisement

Appendix Function Parameter List
P143

Cooling Fan ON-OFF Control Select

・Operation modes of cooling fan in normal status and fault status can be set.
Setting
value
Operation of cooling fan
Power-on: ON
0
Power-off :OFF
Power-on: ON
1
Heat sink temperature is
below 100 ℃: OFF
Power-on: ON
2
Power-off :OFF
Power-on: ON
3
Heat sink temperature is
below 100 ℃: OFF
・The parameter is invalid to models without cooling fan (1-phase 200 V/ 0.2 to
0.75 kW model and 3-phase 400 V/0.75 kW model).
P144

Input Terminal Filter

Filter constant of control circuit terminals (No.2 to No.8) can be set in the
inverter to effectively remove interference of external signal input.
Setting value (times)
・If the setting value is too high, the interference resistance capability will be
enhanced, but response speed of control input terminals will decrease.
・If the setting value is too low, the interference resistance capability will be
weakened, but response speed of control input terminals will increase.
・When start/stop, forward run and reverse run signal (terminal No.2 and No.3)
are used to operate the inverter, internal processing time of the inverter will
become longer even if the setting value is low. In this case, response speed of
control input terminals will be slower than other terminals.
256
Details
5 to 100 (Increment = 1)
Operation when heat sink
is faulty
The inverter stops
abnormally.
The inverter stops
abnormally.
The inverter does not stop
but sends out alarm.
The inverter does not stop
but sends out alarm.