8.2 Setting Built-in Memory Parameters

The contents of built-in memory parameters "E001" to "E182" are identical to
those of function parameters "P001" to "P182". The setting value of build-in
memory parameter can be changed in "Built-in Memory Setting Mode".
Setting Example
Change the maximum output frequency from 50.0 Hz to 60.0 Hz (change
setting value of built-in memory parameter E008 from "50.0" to "60.0").
1. Press
button to stop the inverter.
2. Press
button four times.
(If a password is set beforehand, please enter it. Refer to
parameter P150. )
3. Press
button twice to select Built-in Memory Setting
Mode.
(If the mode is not displayed, set function copy function 4 to
"E2P".)
4. Press
button seven times to change the built-in
memory parameter No. to "E008".
5. Press
button to display setting value of built-in memory
parameter E008. (The display part is flickering.)
6. Press
button to change the displayed value to
"60.0".(The display part is flickering.)
7. Press
button to apply the value.
8. Press
button to enter "operation ready" status.
That's to say, the inverter is in normal stop status and can be
operated if required. (Operation Status Display Mode)
8. Setting Modes and Copy Functions of Built-in Memory