Appendix Function Parameter List
P092

Output RY Function Select

Functions of relay output (control circuit terminal A, B and C) can be set.
・Energizing in ON status: The relay is turned ON when the coil is energized.
・Non-energizing in ON status: the relay is turned ON when the coil is not
energized.
Setting value
Energizing
Non-energizing
in ON
in ON status
status
0
1
2
3
4
5
6
7
8
214
(Signal ON status = ON between terminals A and
C, OFF between terminals B and C)
(Signal ON status = OFF between terminals A
and C, ON between terminals B and C)
Function
r0
Run signal
r1
Reverse run signal
r2
Arrival signal
r3
Overload alarm
r4
Frequency sensing
r5
Current sensing (1)
r6
Current sensing (2)
r7
Fault alarm (1)
r8
Fault alarm (2)
ON conditions for relay
With run signal ON or during
inverter output
When inverter is in reverse run
status
When output frequency is within
±2 Hz of setting frequency
When the output current is above
140% of the rated current or the
electronic thermal level is
reached.
When the output frequency is
above sensing frequency
(parameter P094 setting).
When the output current is above
the sensing current level
(parameter P095 setting).
When the output current is below
the sensing current level
(parameter P095 setting).
During fault trip occurrence in the
inverter.
When the inverter is in normal
status (OFF for fault trip status).