P024£ºStart mode
This parameter sets the starting operation for the case that an externally set run signal is input
when the power is turned ON.
!
Caution
•EThe factory setting is "1" (OP stop).
•EIf the value is set to "0", operation starts immediately when the power is turned ON.
•EIf the value is set to "2", operation starts after the wait time has elapsed after the power is turned ON.
Data
setting
Operation
value
0
Run
1
"OP" stop
Operate after
2
wait time
"OP" stop
3
76
Depending on the start mode setting, when the run signal is ON, the inverter
may start (restart) suddenly if the power is turned ON or the power is restored
after a power failure. Keep out of the machine.
Design the machine so that personal safety can be ensured even if the inverter
starts suddenly.
Failure to do so could lead to injury.
Depending on the start mode function setting, if the fault trip is reset with the
run signal being ON, the inverter may restart suddenly.
(Reset the trip after ensuring personal safety.)
Failure to do so could lead to injury.
Operation starts immediately when the power is turned ON and the low
voltage level (LU level) is exceeded.
The inverter OP trips when the power is turned ON and the low voltage
level (LU level) is exceeded. Turn the start input signal OFF once, reset
the inverter and then turn the run signal ON again to resume operation.
The inverter starts when the power is turned ON, the low voltage level
(LU level) is exceeded and the wait time is passed.
(The wait time is set with parameter P026.)
The inverter OP trips when the power is turned ON and the low voltage
level (LU level) is exceeded. Turn the start input signal OFF once, reset
the inverter and then turn the run signal ON again to resume operation.
(This setting will function in the same manner as data "1" if the run signal
is ON when the power is turned ON. However, starting after the wait time
has elapsed is possible during normal startup.)
Details of operation