Appendix Function Parameter List
P101

0 V Stop Function Select

When the frequency setting signal is lower than than setting value, the
inverter output can be stopped by using 0 V stop function.
Data setting range
0000·0.5 to 400.0
(Hz)
・Setting value "0000"
:0 V stop function disabled
・Setting value "0.5 to 400.0" :0 V stop function enabled (0 V stop frequency
setting)
■ 0 V stop function
・When the frequency signal is set to "analog setting (parameter P004 = "0",
"2", "3", "4", "5", "6" and "8"), the inverter will stop output after the frequency
setting signal reaches the setting value of 0 V stop function select.
・0 V stop will not be performed if 0 V stop function select is set to "0000".
The inverter will continuously run at the lower frequency limit if the frequency
setting signal is lower than 1/100 (1%) of full scale.