P016
Electronic Thermal Select
Thermal Current Setting
P017
Electronic thermal operation level can be set when motor overload is detected
and the inverter output needs to be stopped.
Operation coasts to stop when OL is displayed.
■ Parameter P016: Electronic Thermal Select
Setting
Validity of
value
function
0
1
2
3
*About frequency derating
The function can automatically compensate operation level when motor
cooling performance drops during low-speed operation.
■ Parameter P017: Thermal Current Setting
Data setting range (A)
* Please make settings according to the rated current of the applicable motor.
■ Example of setting current and thermal operation (P016=1)
・Setting current ×100% ⇒ Does not operate
・Setting current ×125% ⇒ Operate (OL trip)
OL trip will occur if the inverter current remains 140% of its
×
rating for 1 minute.
○
The output frequency is not derated
○
The output frequency is derated
○
Forced air-cooled motor specification
0.1 to 100.0
Appendix Function Parameter List
Details of function