■ Setting procedure when vector control is selected

1) Control method select: Vector control select (set P129 to "1").
2) Motor capacity select : Capacity of motor in use is set to "P130: Motor
3) Motor polarity setting : Motor polarity to be used can be set with "P131:
4) Trial operation
5) Motor constant setting : When motor constant is known beforehand
6) Trial operation
Capacity).(0.4 to 15kW)
Motor capacity = Inverter capacity (factory setting)
If the motor capacity is equal to the inverter, no
additional setting will be required.
Motor Pole Number".(2/4/6 poles)
Factory setting of motor polarity is 4-pole.
If the motor polarity is 4-pole, no additional setting
will be required.
: If required motor characteristics have been acquired, it
indicates that the setting is complete.
(Operation under motor constant is recommended
by our company.)
If the required motor characteristics have not been
acquired, the following settings need to be made.
・Setting of "P133: Voltage Compensation
Constant"
・Setting of "P134: Slip Compensation Frequency"
When motor constant is unknown beforehand,
automatic tuning will be performed.
・"P132: Motor Constant Measuring Function" can
be set to "1" to measure voltage compensation
constant.
・"P132: Motor Constant Measuring Function" can
be set to "2" to measure slip compensation
frequency.
: If required motor characteristics have been acquired, it
indicates that the setting is complete.
If required motor characteristics have not been
acquired after setting motor constant through P133
and P134, automatic tuning will be performed.
Appendix Function Parameter List
245