Appendix Function Parameter List
P149

Upper Current Limit of Alarm LED

When alarm LED operation select is set to "1" or "3", the upper current limit to
judge overload fault alarm can be set with this parameter.
If output current of inverter is higher than setting value, the alarm LED will
flicker as overload fault alarm.
Data setting range (A)
Related parameter: P147
P150

Password

To prevent accidental changes to the data after parameter setting is complete,
password can be set with this parameter.
Data setting range
* "0000" indicates that there is no password.
To set a password, press MODE button in "control status monitor mode" and
password input display switches to "PS". After entering the password and pressing
SET button, you will have access to "custom mode", "function setting mode" and
"built-in memory setting mode".
If you do not enter the password when password input display switches to "PS",
the display will return to "operation status display mode" as MODE button is
pressed.
260
0.1 to 100.0
0000·1 to 9999