9.2.2 Resetting Fault Trips

If the abnormality indicator in the display part of operation panel lights up and
operation is stopped, please handle the abnormality before resetting operation.
Reset by
The reset can be made by cutting off the power once.
power
(The inverter can operate when powered on again.)
1 For the operation in panel setting mode (parameter P003 is set to "0" or
Reset by stop
2 For the operation in external control mode (parameter P003 is set to "2" or
signal
For the operation in external control or communication setting mode
(parameter P003 is set to "4", "5" or "7"), the reset cannot be made even if
OPERATION COMMAND button designed for external control or
Reset by panel
communication is turned OFF once.
Press STOP button on operation panel to reset, and then restart the
inverter.
Reset by
When parameter P036 to P040 are set to "1", turn the function setting
multi-function
switch ON once and OFF again to perform the reset.
terminal
Then restart the unit again.
Reset by
communication
Write 0x9696 into register No. 253 (DT253) to reset the inverter.
command
"1"), press STOP button on operation panel to reset, and then restart the
inverter.
"3"), turn off OPERATION COMMAND button designed for external
control once to reset, and then restart the inverter.
Note) Reset by stop signal cannot be made through communication.
9. Troubleshooting