5.7

Meter setting and adjustment

 : Meter selection
 : Meter adjustment gain
Refer to section 3.4 for details.
5.8

Forward/reverse run selection (Panel keypad)

 : Forward/reverse run selection (Panel keypad)
 Function
Program the direction of rotation of the motor when the running and stopping are made using the RUN
5
key and STOP key on the operation panel.
Valid when  (command mode) is set to  (operation panel).
[Parameter setting]
Title

Function
Forward/reverse run selection
(Panel keypad)
Using extension panel RKP007Z (option) : When  is set to  and the standard monitor is displayed,
pressing the FWD/REV key changes the direction of rotation from forward to reverse after displaying the
message .
Pressing the FWD/REV key again changes the direction of rotation from reverse to forward after
displaying the message .
Using extension panel RKP002Z (option) : When  is set to  and the standard monitor is displayed,
pressing the DOWN key while pressing the ENT key changes the direction of rotation from forward to
reverse after displaying the message .
Pressing the UP key while pressing the ENT key again changes the direction of rotation from reverse to
forward after displaying the message .
Check the direction of rotation on the status monitor. Refer to section 8.1 for details about monitor.
: Forward run
: Reverse run
When the F and R terminals are used for switching between forward and reverse rotation from the
terminal board, the  forward/reverse run selection parameter is rendered invalid.
Short across the F-CC (Sink logic) or P24-F (Source logic) terminals: forward rotation
Short across the R-CC (Sink logic) or P24-R (Source logic) terminals: reverse rotation
Adjustment range
0: Forward run
1: Reverse run
2: Forward run (F/R switching on
extension panel)
3: Reverse run (F/R switching on
extension panel)
E-14
E6581697
Default setting
0