Toshiba TOSVERT VF-MB1 Instruction Manual page 51

Industrial inverter for 3-phase induction motors
Hide thumbs Also See for TOSVERT VF-MB1:
Table of Contents

Advertisement

SINK (Negative) logic (When an external power supply is used)
The P24 terminal is used to connect to an external power supply or to separate a terminal from other input
or output terminals.
<Examples of connections when an external power supply is used>
2
Switching of slide switch
Refer to section 1.3.3 3) about location of slide switch.
(1) Switching of sink/source logic: SW1 (Default setting : PLC side)
(2) Switching of S3 terminal function: SW2 (Default setting : LOGIC side)
Slide switch SW1 : PLC side
24V
DC
Common
Output
24V
DC
Input
Common
Programmable
controller
Setting of sink/source logic for F, R, RES, S1, S2, and S3 terminals are switched by slide switch SW1.
When an external power supply is used for sink logic, set the slide switch SW1 to PLC side.
Set the sink/source logic switching before power supply switches on.
After confirming the right for sink/source setting, power supply switches on.
Setting of logic input/ PTC input for S3 terminal is switched by slide switch SW2 and parameter 47.
When using S3 terminal as a logic input terminal, set the slide switch SW2 to LOGIC side and set the
parameter =.
When using S3 terminal as a PTC input terminal, set the slide switch SW2 to PTC side and set the
parameter =.
Match the setting of slide switch SW2 and parameter  surely.
If it is not, this can result in malfunction.
Sink (Negative) logic
24V
DC
P24
SW1: PLC side
F
CC
OUT
NO
Inverter
B-12
E6581697
Input
Output