Title
Function
Acceleration time 2
f500
Deceleration time 2
f501
Selecting an acceleration/deceleration
f504
pattern
f510 Acceleration time 3
f511 Deceleration time 3
Setting of acceleration/deceleration
f519
time unit
Default setting is 0.1s unit. Acceleration/deceleration time unit can be changed to 0.01s unit by f519 = 1
setting. The value of f519 return to 0 after setting.
1)
Selection using parameters
Output frequency [Hz]

0

=
=
=
Acceleration/deceleration time 1 is initially set as the default. Acceleration/deceleration time 2 and 3 can
be selected by changing the setting of the f504 .
Enabled if cmod =  (panel input enabled)
2)
Switching by frequencies - Switching the acceleration/deceleration time automatically at the frequency
setting of f505 .
Title
Function
Acceleration/deceleration 1 and 2
f505
switching frequency
Acceleration/deceleration 2 and 3
f513
switching frequency
Note: Acceleration/deceleration patterns are changed from pattern 1 to pattern 2 and from pattern 2 to pattern 3
in increasing order of frequency, regardless of the order in which frequencies are changed. (For example,
if f505 is larger than f513 , f513 pattern 1 is selected in the frequency range below the frequency
set with f505 . )
0.0-3600 (0.00-360.0) [sec]
0.0-3600 (0.00-360.0) [sec]
1: Acceleration/deceleration 1
2: Acceleration/deceleration 2
3: Acceleration/deceleration 3
0.0-3600 (0.00-360.0) [sec]
0.0-3600 (0.00-360.0) [sec]
0: -
1: 0.01s unit (after execution: 0)
2: 0.1s unit (after execution: 0)


0.0 (disabled)
0.1-  (Hz)
0.0 (disabled)
0.1-  (Hz)
F-77
Adjustment range



Adjustment range
E6581697
Default setting
10.0
10.0
1
10.0
10.0
0
6
Time [s]
Default setting
0.0
0.0