Logic sequence parameters
Communication
Title
Function
No.
Input function
A900
target 11
Input function
A901
command 12
Input function
A902
target 12
Input function
A903
command 13
Input function
A904
target 13
Output function
A905
assigned object 1
Input function
A906
target 21
Input function
A907
command 22
Input function
A908
target 22
Input function
A909
command 23
Input function
A910
target 23
Output function
A911
assigned object 2
Minimum
setting unit
Unit
Adjustment range
Panel/Commun
ication
-
-
Input terminal function number
0: No function
1: Terminal F
2: Terminal R
3: Terminal RES
4: Terminal S1
5: Terminal S2
6: Terminal S3
7: Terminal VIB
8: Terminal VIA
9 to 20: -
21 to 24: Virtual input terminal 1 to 4
25 to 32: Internal terminal 1 to 8
918 to 934: Logic sequence function
1000 to 1255: Output selection number
2000 to 2099: FD00 to FD99
3000 to 3099: FE00 to FE99
-
-
0:NOP (not operation)
1:ST (move)
2:STN
3:AND (logical product)
4:ANDN
5:OR (logical sum)
6:ORN
7:EQ (equal)
8:NE (not equal)
9:GT (greater than)
10:GE (greater or equal)
11:LT (less than)
12:LE (less or equal)
13:ASUB (absolute)
14:ON (on delay timer)
15:OFF (off delay timer)
16:COUNT 1 (counter 1)
17:COUNTR 2 (counter 2)
18:HOLD (hold)
19:SET (set)
20:RESET (reset)
21:CLR
22:CLRN
-
-
0-3099 (Same as a900)
-
-
0-22 (Same as a901)
-
-
0-3099 (Same as a900)
-
-
0-3099 (Same as a900)
-
-
0-3099 (Same as a900)
-
-
0-22 (Same as a901)
-
-
0-3099 (Same as a900)
-
-
0-22 (Same as a901)
-
-
0-3099 (Same as a900)
-
-
0-3099 (Same as a900)
K-27
Default
setting
0
number
0
0
0
0
0
0
0
0
0
0
0
E6581697
User
Reference
setting
6.36
11