<Example of operation>
1) Output terminal function: 28 (OT) Over-torque detection
Over-torque
signal output
-
6

6.24.11 Cooling fan control selection

f620 : Cooling fan ON/OFF control
 Function
f620 = 0 : Cooling fan automatically controlled. Cooling fan operates only when the ambient temperature is
f620 = 1 : Cooling fan not automatically controlled. Fan is always running when the inverter is on.
[Parameter setting]
f620 Cooling fan ON/OFF control
f615 = 0 (Alarm only)

Torque (%)
When f615 = 1 (tripping), the inverter will trip if over-torque lasts for the period of time set with
f618 . In such a case, the over-torque signal remains ON.
Set to operate the fan only when the ambient temperature is high during operation. When the inverter
is on, the service life of the cooling fan is longer than if it is always running.
high during operation.
If the ambient temperature is high, even when the inverter is stopped, the cooling fan automatically
operates.
Title
Function
less than 
Time [sec]
Adjustment range
0: ON/OFF control
1: Always ON
F-88
E6581697
OFF
ON
OFF

Default setting
0