6.7
Operation frequency
6.7.1
f240 : Starting frequency
Function
[Parameter setting]
f240
6
Starting frequency
The frequency set with is put out as soon as operation is started.
Use the parameter when a delay in response of starting torque according to the
acceleration/deceleration time is probably affecting operation. Setting the starting frequency to a
value from 0.5 to 3.0Hz is recommended. The occurrence of an overcurrent can be suppressed by
setting this frequency below the rated slippage of the motor.
Title
Function
Starting frequency
Output frequency (Hz)
Starting frequency
Operation signal (F-CC)
Adjustment range
0.1-10.0 (Hz)
0
F-22
E6581697
Default setting
0.5
Time
ON
OFF