6.24.16 Motor PTC thermal protection
f147 : Logic input / PTC input selection (S3)
f645 : PTC thermal selection
f646 : Resistor value for PTC detection
 Function
[Parameter setting]
f147 Logic input / PTC input selection (S3)
f645
6
f646
Note : Protecting PTC thermal, set f147 = 1 (PTC input) and slide switch SW2 to PTC side.
Tripping level is defined by f646 setting. Alarm level is defined by 60% of f646 setting.
Connect the PTC of PT100 characteristic between S3 and CC terminals.
Detection temperature can be set by f646 setting.
[Connection]
Output of PTC input alarm signal
The PTC input alarm is assigned to the output terminal.
Setup example) When the PTC input alarm is assigned to the OUT terminal
f131
Setting value 151 is reverse signal.
This function is used to protect motor from overheating using the signal of PTC built-in motor.
The trip display is " e-32 ".
Title
Function
PTC thermal selection
PTC detection resistor value
PT100
Title
Function
Output terminal selection 2A
(OUT)
Adjustment range
0: Logic input
1: PTC input
1: Tripping
2: Alarm only
100-9999 ( Ω )
S3
CC
Adjustment range
0-255
F-92
E6581697
Default setting
0
1
3000
Setting
150: PTCA
(PTC input alarm signal)