3) Control circuit terminal board
1
Stripping length: 6 (mm)
Screwdriver: Small-sized flat-blade screwdriver
(Blade thickness: 0.6 mm, blade width: 3.5 mm)
Refer to section 2.3.2 for details about all terminal functions.
Wire size
Recommended ferrule
Using ferrule to be improved efficiency and reliability of wiring is recommended.
*2
*2
*1: Crimping pliers
*2: These ferrules enable practical crimping of two wires in a ferrule.
The control circuit terminal board is common to all equipment.
SW1
SOURCE
PLC
SINK
SW2 (S3)
LOGIC
PTC
Default setting is PLC side and LOGIC side.
Recommended
Screw size
tightening torque
0.5 Nm
M3 screw
4.4 lbin
Conductor
Solid
0.3-1.5mm
Stranded
Wire size
2
mm
(AWG)
0.34 (22)
0.5 (20)
0.75 (18)
1 (18)
1.5 (16)
2 X 0.5 (-)
2 X0.75 (-)
CRIMPFOX ZA3 (PHOENIX CONTACT), CT1 (Dinkle International., Ltd)
1 wire
2
(AWG 22-16)
Type
PHOENIX CONTACT
AI 0.34-6TQ
AI 0.5-6WH
AI 0.75-6GY
AI 1-6RD
AI 1.5-8BK
AI TWIN2 X 0.5-8WH
AI TWIN2 X 0.75-8GY
A-14
E6581697
Shorting-bar
2 wires of same size
2
0.3-0.75mm
(AWG 22-18)
Dinkle International.,Ltd
DN00306
DN00506
DN00706
DN01006
DN01508
DTE00508
DTE00708