6.12 Preset-speed frequencies

f287 to f294 : Preset-speed frequency 8 to 15
Refer to section 3.6 for details.

6.13 Bumpless operation

f295 : Bumpless operation selection
f732 : Local/remote key prohibition of extension panel
 Function
6
[Parameter setting]
f295
f732
Set parameter f750 (EASY key function selection) = 2 (Local / remote key).
EASY lamp is lighting, during selecting local mode.
LOC/REM key of extension panel option (RKP007Z) can be used.
In case, set parameter f732 (Local/remote key prohibition of extension panel) = 0 (Permitted).
When switching from Remote mode to Local mode, the status of start and stop, and operating
frequency at Remote mode are moved to Local mode.
By contraries, when switching from Local mode to Remote mode, they are not moved to Remote
mode.
Title
Function
Bumpless operation selection
Local/remote key prohibition of
extension panel
EASY
key is assigned to Local/remote function.
Adjustment range
0: Disabled
1: Enabled
0: Permitted
1: Prohibited
F-30
E6581697
Default setting
0
1