Toshiba TOSVERT VF-MB1 Instruction Manual page 221

Industrial inverter for 3-phase induction motors
Hide thumbs Also See for TOSVERT VF-MB1:
Table of Contents

Advertisement

[Parameter setting]
Title
f681 Analog output signal selection
f684 Analog output filter
Inclination characteristic of analog
f691
output
Analog output bias
f692
Note 1: With 0 to 20mAdc (4 to 20mAdc) output, or 0 to 10Vdc output, set f681 to 1 or 2 .
■ Example of setting
f681 =1, f691 =1, f692 =0(%)
(mA)
20
0
0
Internal calculated v alue
f681 =1, f691 =0, f692 =100(%)
(mA)
20
0
0
Internal calculated value
The analog output inclination can be adjusted using the parameter  .
Function
0: Meter option (0 to 1mA)
1: Current (0 to 20mA) output
2: Voltage (0 to 10V) output
2-1000 (ms)
0: Negative inclination (downward slope)
1: Positive inclination (upward slope)
-1.0 - +100.0 (%)
100%
: Large gain
100%
F-101
Adjustment range
f681 =1, f691 =1, f692 =20(%)
(mA)
20
4
f692
0
Internal calculated value
f681 =1, 691 =0, f692 =100(%)
(mA)
20
: Small gain
f692
4
0
Internal calculated value
E6581697
Default setting
0
2
1
0.0
6
100%
100%