5) Overload characteristic selection aul
Overload characteristic of inverter can be selected to 150%-60s or 120%-60s.
[Parameters settings]
Title
Regarding to characteristic for = 1 setting, refer to section 3.5.3).
3
Note 1) In case of = 2 setting, be sure to install the input AC reactor (ACL) between power supply and inverter.
= (Variable torque characteristic), = (120%-60s)
Inverter overload
time [s]
Function
Overload characteristic selection
60
0
105%
Inverter overload protection characteristic
Adjustment range
0: -
1: Constant torque
characteristic ( 150%-60s )
2: Variable torque
characteristic ( 120%-60s )
Current
[%]
106
110
115
120
140
165
Monitored output current [%]
120%
100%: Inverter rated output current
C-22
Default setting
0
Inverter overload time [s]
(Outline data)
900
180
90
60
2
0.5
E6581697