Toshiba TOSVERT VF-MB1 Instruction Manual page 339

Industrial inverter for 3-phase induction motors
Hide thumbs Also See for TOSVERT VF-MB1:
Table of Contents

Advertisement

(Continued)
Error code







/

/


Note 2)


Note 2)  is blinking after power supply is on. In this time, the keys are not operated.
[Prealarm display]
13

If two or more problems arise simultaneously, one of the following alarms appears and blinks.
, , 
The blinking alarms , , , h, t are displayed in this order from left to right.
Problem
Output frequency
 An attempt was made to operate at a
upper limit
frequency higher than 10 times the base
frequency ( or ).
Operation panel key
 The RUN or STOP key is held down for
alarm
more than 20 seconds.
 The RUN or STOP key is faulty.
S3 terminal alarm
 Slide switch SW2 and parameter f147
settings are different.
Auto-tuning
 Auto-tuning in process
Break in analog
 The signal input via VIC is below the
signal cable
analog signal detection level set with
 and setting value of  is
one or more.
In forced operation
 "" and operation frequency is
displayed alternately in operation of forced
fire-speed control.
STO signal OFF
 STO terminal is in open-circuit.
Password verification
 After the password setting (f738), the
result
password was input to f739 (password
verification).
Switching display of
 The EASY key was pushed in the
Easy setting mode /
standard monitor mode.
Standard setting
mode
Input requirement of
 A region setting is not input yet.
region setting
 Power supplied to the inverter at first time
 As checking the region setting parameter
set is set to 0, inverter return to default
setting.
 As typ is set to 13, inverter return to
default setting.
No trip of past trip
 No new record of past trip, after past trips
were clear.
No detailed
 The detailed information of past trip is
information of past
read by pushing the center of setting dial
trip
during blinking nerr ⇔ number.
But parameter set is lighting as same as other parameters and is not blinking.
Overcurrent alarm
Overvoltage alarm
Overload alarm
Overheat alarm
Communication alarm
Possible causes
Same as  (overcurrent)
Same as  (overvoltage)
Same as  and  (overload)
Same as  (overheat)
Same as err5 (communication fault)
M-6
Remedies
 Operate at a frequency within 10 times the
base frequency.
 Check the operation panel.
 Match the settings of SW2 and f147.
 Power supply OFF and ON after these
settings.
 Normal if it the message disappears after a
few seconds.
 Check the cables for breaks. And check the
setting of input signal or setting value of
 and .
 It is normal the alarm is gone out after the
forced fire-speed control operation.
 Close STO and + SU circuit.
 If the password is correct, pass is displayed
and if it is incorrect, fail is displayed.
 When easy is displayed, setting mode
becomes easy setting mode. When std is
displayed, it becomes standard setting mode.
Set a region setting by using setting dial.
Refer to section 3.1.
 Normal operation.
 Normal operation.
To be returned by pressing MODE key.
E6581697