InfiniBand FDR Switch Platform Hardware User Manual
3. Decide which side of the rack you want the data connectors.
You will most likely need extra room for cable bending on the connector side of the chassis
and should plan to keep the spine side as close to the rack door as possible, thus having more
room for the cables.
4. Measure the distance between the vertical supports and adjust the shelf brackets
according to this distance. This chassis can be installed in a rack with a distance
between the vertical supports of from 65cm(25.6in.) to 80cm(31.5in.).
Mellanox Technologies

Figure 5: Vertical Rack Supports Dimension

Figure 6: Placement of Chassis in Rack

Doors
Shelf
Chassis
Insufficient room for recommended
bending radius
Doors
Cable with
recommended
bending radius
Connector side
Spine side
Vertical
supports
24
Rev 1.7