1. Place the cable holder next to the rack, on the connector side of the chassis, and iden-
tify the holes where the caged nuts were placed in step 4
2. Set the bottom of the cable holder at the level of the shelf.
3. Screw the cable holder onto the rack using the screws provided.
4. Repeat steps 1- 3 for the second cable holder.
5. Install the shelves. The cable support shelves just sit on the cable holders.
6. Use the holes in the shelves to tie down the cables individually or in bundles.
1.7.5

Ground Connections

Make sure to connect the ground post to a valid electrical ground. Use a grounding lug
and a ground wire of sufficient capacity to safely convey a potential discharge. The
grounding post is M-8 with 1.25mm pitch threads. A ground wire of AWG 6 or 4mm
diameter is recommended for grounding this device. The chassis is concurrently
grounded through each of the PSUs. Only connect the PSU cords to properly grounded
outlets. Do not rely on the PSU grounds. It is absolutely necessary to connect the ground-
ing post. Make sure the connections are solid and permanent. If you choose to not use the
ground screw, make sure that the rack is properly grounded and that there is a valid
ground connection between the chassis of the switch and the rack. Test the ground using
an Ohm meter.
1.8

Power Connections

The switch includes integrated hot-swap power supplies which support up to 10 load-
sharing 1000W or 1600W supply units. The slots for the power supply units (PSUs) are
Mellanox Technologies
The cable holders should go to the outside of the vertical supports.
If the cable holder is not set properly the upper bracket will not line up with the cable
holder.
Use Velcro ties to tie down the cables. Electric cable ties are not recommended.

Figure 29: Ground Connection

Grounding post
Rev 1.7
37