InfiniBand Switch Platform Hardware User Manual
15. Equipment Disposal
16. Local and National Electrical Codes
17. Installation Codes
18. Battery Replacement
19. UL Listed and CSA Certified Power Supply Cord
20. High Leakage Current
Mellanox Technologies
Disposal of this equipment should be in accordance to all national laws and regula-
tions.
This equipment should be installed in compliance with local and national electrical
codes.
This device must be installed according to the latest version of the country
national electrical codes. For North America, equipment must be installed in
accordance to the applicable requirements in the US National Electrical Code
and the Canadian Electrical Code.
Warning: Replace only with UL Recognized battery, certified for maximum
abnormal charging current not less than 4mA
There is a risk of explosion should the battery be replaced with a battery of an
incorrect type.
Dispose of used batteries according to the instructions.
For North American power connection, select a power supply cord that is UL Listed
and CSA Certified, 3 - conductor, [16 AWG], terminated with a molded plug rated at
125 V, [13 A], with a minimum length of 1.5m [six feet] but no longer than 4.5m.
For European connection, select a power supply cord that is internationally
harmonized and marked "<HAR>", 3 - conductor, minimum 1.0 mm
rated at 300 V, with a PVC insulated jacket. The cord must have a molded plug
rated at 250 V, 10 A.
Warning: High leakage current; Earth connection essential before connecting supply.