3. Press the DATA/SHIFT key for a minimum of one second, and the
display will be as shown below.
4. Input the value (0001) and press the MODE/SET key. The display
will change as shown below and the write protection will be
established.
5. Press the DATA/SHIFT key for a minimum of one second to return
to the Auxiliary Function mode display.
This completes the procedure for setting the write protection. The new
password setting will be valid after the next power OFF/ON cycle.

7.2.13. Clearing the Option Unit Detection Alarm

Alarm A.E7 (option unit detection failure) occurs the first time that the
XtraDrive servo amplifier is turned ON after disconnecting an option
board.
Initialize the parameter settings with the servo OFF.
After performing the procedure, cycle the power to reset all parameters to the default settings.
Because the parameter has been set for the XtraDrive connected to an option board,
be sure to adjust the setting or initialize the parameter value (Fn005 of the Auxiliary Function
mode) to meet the current system needs.
Flashing for
one second
IMPORTANT
7-37
Chapter 7: Using the Panel Operator