Manual Gain Adjustment of Analog Monitor Output
Follow the procedure below to execute the manual gain adjustment of
analog monitor output.
1. Press the MODE/SET key to select the Auxiliary Function mode.
2. Press the Up Arrow or Down Arrow key to select parameter Fn00D.
3. Press the DATA/SHIFT key for at least one second, and the display
will be as shown below.
4. Press the MODE/SET key. Each time the MODE/SET key is
pressed, the monitor output will toggle between the displays for the
two channels shown below.
5. Press the DATA/SHIFT key for less than one second, and the
analog monitor gain parameter will be displayed. Pressing the
DATA/SHIFT key again for less than one second will return to the
display shown in steps 3 or 4 above.
6. Press the Up Arrow or Down Arrow key to adjust the gain for the
analog monitor output.
7. When gain adjustment has been completed for the two channels,
press the DATA/SHIFT key for a minimum of one second to return
to the Auxiliary Function mode display.
This completes the manual gain adjustment of the analog monitor
output.