Data Logging On Tuning Screens - Omron CX-PROCESS TOOL V5.2 - 12-2009 Operation Manual

Table of Contents

Advertisement

Tuning
Block name (model)
Target function block
Display
Example:
Basic or Advanced PID
Settings
Example:
Basic or Advanced PID

4-7-2 Data Logging on Tuning Screens

Starting Logging
Logged Data
In
chronological
order
• Select the Save Trend Data to log data and save it in a CSV file. The default
location for the CSV file is in the current directory with a file name of
CSVTagNameInFunctionBlock_PresentTime.csv. The present time is in
the form YYYY/MM/DD_HH/MM/SS. Click the Browse Button to change
the storage location.
3. The Tuning Screen will be displayed. The following settings can be dis-
played and set.
Control Block: Basic PID (011), Advanced PID (012), Batch flowrate capture (014),
Indication and Setting (031), Indication and Operation (032), Ratio Setting (033),
Indicator (034), blended PID (013), 2-position ON/OFF (001), 3-position ON/OFF (002),
Segment Program 2 (157)
SP, PV, and MV trends
Setting values for P, I, D, and MV limit High/Low, High/High Alarm, High Alarm, Low
Alarm, Low/Low Alarm, and Deviation Alarm.
Alarm OFF switch, Stop block operation command, SP, PV, MV, and A/M status, R/L
status (See note 1.), bar color change if alarm occurs.
Setting values for P, I, D, and MV limit High/Low, High/High Alarm, High Alarm, Low
Alarm, Low/Low Alarm, and Deviation Alarm.
SP, MV (manual mode only), A/M switching (See note 1.), R/L switching (See note 1).
Note Refer to 4-7-3 Screen Configuration below for details on the screen configura-
tions and setting procedures.
4. To close the Tuning Screen, click the X Button in the upper-right corner of the
window. If data logging is being performed at the time, the logging file will be
saved when the Tuning Screen is closed.
Note With CX-Process Tool version 3.2 or higher, up to four Tuning Screens can be
opened at the same time. Opening more Tuning Screens, however, will increase
the communications load and can cause large errors in the data monitoring/log-
ging refresh cycle.
Data logging is started when the Tuning Screen is opened.
The following ITEM data is logged for each function block in the Tuning Screen.
Tuning Screen
1,Basic PID
Record
Record
Record
YYYY/MM/DD
HH/MM/SS
If the refresh cycle is set to 200 ms, the multiple
data for 1 second will be stored as one entry
because the CSV file format is for data every
second.
Signal source Function Block or ITEM
Block address and function block name
Tag name
ITEM name, ITEM name, etc.
ITEM data (in the same order as ITEM
names above, tab-delimited)
Section
4-7
295