Validating Sequence Table Operation (Lcb05/05D Only) - Omron CX-PROCESS TOOL V5.2 - 12-2009 Operation Manual

Table of Contents

Advertisement

Operation Check
Restarting Function
Blocks

4-6-7 Validating Sequence Table Operation (LCB05/05D Only)

Entering Sequence Table
Validate Action Mode
1, 2, 3...
Click the Start Block Operation Button in the Execute Dialog Box to make the
operation of the function block displayed in the block address (the basic PID in
block address 001 in the following case) resume.
The operation of a sequence table in a Loop Controller can be validated
(Sequence Table Validate Action Mode). The following can be checked in a
sequence table (block model 302):
• Current step number
• Rule conditions (met/not met)
• Condition signal conditions (met/not met)
• Action signal conditions (met/not met)
Sequence Table Validation
Loop Controller
Use the following procedure to enter Sequence Table Validate Action Mode.
1. Select the sequence table block and select Edit/Sequence Table from the
Settings Menu. The sequence table will be displayed.
CX-Process
Tool
The current step number,
condition-met rules,
condition-met signals, and
condition-met actions are
displayed in color.
Sequence table
Rule
Step
Contact
Next
step
Section
4-6
281