Function Blocks/Items Incompatible With Earlier Versions; Incompatibility With Versions Earlier Than Version 5.0 - Omron CX-PROCESS TOOL V5.2 - 12-2009 Operation Manual

Table of Contents

Advertisement

Function Blocks/ITEMs Incompatible with Earlier Versions

1-5-4 Incompatibility with Versions Earlier than Version 2.50
Function Blocks
Incompatible with Earlier
Versions
28
eration screen on CX-Process Tool beforehand that the content of ITEM 099
onwards in the System Common block (Block Model 000) is as follows:
ITEM
099
The following function blocks can be used only with version 2.50 or later versions
of the CS1W-LC001 Loop Control Unit and version 2.50 or higher versions of the
CX-Process Tool.
Fuzzy Logic (Block Model 016), Range Conversion (Block Model 127),
Ramped Switch (Block Model 167), Level Check (Block Model 210), AI4
Terminals from DRT1-AD04 Unit (Block Model 588), and AO2 Terminals
from DRT1-DA02 Unit (Block Model 589)
• If an earlier version of the Loop Control Unit is used with CX-Process Tool ver-
sion 2.50 or higher, these function blocks can be registered but the data for the
function blocks won't be downloaded to the Loop Control Unit when LCU ele-
ment data is downloaded. (The supported function blocks will be downloaded
normally.)
• If Loop Control Unit version 2.50 or later is used with a lower version of the CX-
Process Tool, these function blocks cannot be registered in the CX-Process
Tool, so they cannot be downloaded to the Loop Control Unit.
If these function blocks have been downloaded to the Loop Control Unit al-
ready, the data for these function blocks won't be uploaded from the Loop Con-
trol Unit. The supported function blocks will be uploaded normally. (If Upload
New is selected, the unsupported function blocks will be empty.)
Data name
MPU/FROM version indication V2.00
Version V2.00 and onwards must be indicated.
Section
1-5
Data