Setting Segment Programs
CS1W-LCB05: 500, 499, 498...
CJ1G-CPU43, 44, 45P: 300, 299, 298...
• When the maximum number of steps to be used is increased, rule #2 is followed. When the number is decreased,
step data blocks are removed in ascending order from the lowest function block address.
Setting Bank Data
To edit bank data, press the Bank Setting Button in the Segment Program 3 Edit Screen. The following Edit Bank
Parameters Window will be displayed. For details on editing, refer to Edit Window Functions.
The items in the Edit Window are as follows:
Horizontal Axis
P, I, and D: Used to set PID parameters.
MH and ML: Used to set the MH and ML values for a connected PID block.
Extra Data 1 to 5: Used to set extra data 1 to 5.
Horizontal Axis
Bank number (1 to 100): Indicates the bank number.
Setting the Maximum Number of Banks to Be Used
The maximum number of banks to be used refers to the number of banks to be used in a single program. A Seg-
ment Program 3 block stores in bank data blocks the bank data to be used in the program. The number of bank
data blocks required depends on the number of banks to be used.
• Up to 15 banks of data can be stored per bank data block. When a maximum of 100 steps is used, 7 bank data
blocks are used.
For example, when 70 banks are used, the maximum number of banks is taken to be 70, and 5 bank data blocks
are automatically registered.
• The banks that can be used can be edited on the Edit Window. Any banks beyond the maximum number of banks
cannot be edited.
332
Appendix C