Omron CP - PROGRAMMING MANUAL 05-2007 Programming Manual page 182

Cp1h/cp1l cpu unit
Table of Contents

Advertisement

Sequence Control Instructions
Flags
Precautions
Program with IL(002)/ILC(003) Interlocks
a
IL
A1
b
IL
A2
ILC
A3
ILC
Execution condition
a
b
OFF
ON
Interlocked
OFF
ON
OFF
Not interlocked
ON
ON
Not interlocked
If there are bits which you want to remain ON in a program section interlocked
by MILH(517) or MILR(518), set these bits to ON with SET just before the
MILH(517) or MILR(518) instruction.
Name
Label
Error Flag
ER
The cycle time is not shortened when a section of the program is interlocked
by MILH(517) or MILR(518) because the interlocked instructions are executed
internally.
This program section is not
controlled by the interlock.
This ILC(003)
instruction is ignored
so ...
Program section
A1
A2
Interlocked
Interlocked
Not interlocked
Operation
OFF
Section 3-4
A3
Not interlocked
(Not controlled by
the IL(002)/
ILC(003) interlock.)
149

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents