Floating-point Math Instructions
Operand Specifications
Description
506
Area
CIO Area
Work Area
Holding Bit Area
Auxiliary Bit Area
Timer Area
Counter Area
DM Area
Indirect DM addresses
in binary
Indirect DM addresses
in BCD
Constants
Data Registers
Index Registers
Indirect addressing
using Index Registers
SQRT(466) calculates the square root of the 32-bit floating-point number in
S+1 and S and places the result in R+1 and R. (The floating point source data
must be in IEEE754 format.)
S+1
R+1
The source data must be positive; if it is negative, an error will occur and the
instruction will not be executed.
If the absolute value of the result is greater than the maximum value that can
be expressed as floating-point data, the Overflow Flag will turn ON and the
result will be output as
The following diagram shows the relationship between the input data and
result.
R
S
CIO 0 to CIO 6142
W0 to W510
H0 to H510
A0 to A958
T0000 to T4094
C0000 to C4094
D0 to D32766
@ D0 to @ D32767
*D0 to *D32767
#00000000 to #FFFFFFFF
(binary)
---
---
,IR0 to ,IR15
–2048 to +2047 ,IR0 to –2048 to +2047 ,IR15
DR0 to DR15, IR0 to IR15
,IR0+(++) to ,IR15+(++)
,–(– –)IR0 to, –(– –)IR15
Source (32-bit floating-point data)
S
Result (32-bit floating-point data)
R
.
S: Input data
R: Result
Section 3-14
R
A448 to A958
---
Need help?