Omron CP - PROGRAMMING MANUAL 05-2007 Programming Manual page 868

Cp1h/cp1l cpu unit
Table of Contents

Advertisement

Serial Communications Instructions
Flags
The following diagram shows the order in which data is sent and the contents
of the send frame for various start and end code settings.
No Start or End Code
Data
Only Start Code
Data
ST
Only End Code
Data
Start and End Code
ST
Data
CR+LF End Code
Data
LF
Start and CR+LF End Code
Data
ST
Data received.
Serial port on Serial Communications Unit
Bytes
1
2
3
N
4
(256 bytes max.)
5
6
Name
Label
Error Flag
ER
Number of bytes
(Specified in allocated
DM Setup Area)
Number of bytes
(Specified in allocated
DM Setup Area)
ED
Number of bytes up to ED:
256 max.
ED
Number of bytes between
ST and ED: 256 max.
CR
Number of bytes up to
CR+LF: 256 max.
CR LF
Number of bytes between
ST and CR+LF: 256 max.
Byte order
0: Most significant bytes first
Most signifi-
cant bytes
15
D
Storage order
D+1
D+2
Byte order
1: Least significant bytes first
Most signifi-
cant bytes
15
D
D+1
D+2
Operation
ON if all of the logical ports are being used or the Com-
munications Port Enabled Flag (A202.00 to A202.07) for
the specified logical port is OFF when the instruction is
executed.
ON if the value of C is not within range.
ON if the value for N is not between 0000 and 0100 hex.
OFF in all other cases.
Section 3-23
Least signif-
icant bytes
8
7
0
1
2
3
4
5
6
Least signif-
icant bytes
8
7
0
2
1
4
3
6
5
835