11. Insert the power cord(s) into the PSU jack(s).
12. Follow the procedures to complete the service action as outlined in the
13. PM replacement is complete.

SERVER MODULES

The VSS2249RQ Storage Server supports two VSSEP1EC Server Modules. To
replace or upgrade any of the remaining internal server module components,
such as an Ethernet add-in card, contact a Viking Enterprise Solutions support
representative to request an RMA.

Replacing a Server Module

Server modules are located in the hot aisle. Extending the enclosure from the
rack to replace a server module is not necessary.
1. Follow the appropriate steps to prepare for a service action included in
2. Identify the VSSEP1EC Server Module requiring service.
3. Ensure all transactions have completed on the server module requiring
| 110 |
a. If replacing both PMs at the same time, repeat steps 4 through 9 to
replace the second PM.
b. If only replacing one PM, skip this step and continue with step 11.
section titled "Returning the CMA" on page 118.
Refer to the section titled "Customer Support" on page 208 for guidance in
obtaining an RMA.
ESD-SENSITIVE DEVICE. Only install the device on a properly grounded electrostatic
discharge (ESD) protection surface to avoid damage to the components. Always utilize
a properly grounded ESD wrist strap or mat during operation or installation of the
device, or when connecting the cables.
CAUTION: Hot-swapping any VSSEP1EC Server Module should be completed within
five (5) minutes to maintain proper system cooling. If replacement will not completed
within five minutes, install a module blank in the empty I/O option slot. Contact a Viking
Enterprise Solutions support representative for information on obtaining a server
module blank.
the section "Releasing the CMA" on page 98.
Refer to Chapter 7 titled "Monitoring the VSS2249RQ Storage Server" that begins
on page 77 for information on identifying the server module requiring service.
the service action.
Chapter 8: System Maintenance
CTC-DOC-002293, Rev A.2