Sam Smart Nozzle Flow Calibration (Password 10610) - Idex Akron Bras SAM BOOST Operation Installation Maintenance Manual

For sam boost with smart nozzle n2p and uv780 display
Table of Contents

Advertisement

SAM BOOST™ WITH SMART NOZZLE N
7.8

SAM Smart Nozzle Flow Calibration (Password 10610)

1. Engage pump while inside calibration screen
a. SAM Boost™ will default the water source from the internal tank. The nozzles will
2. Wake up nozzle by pressing a button
a. Verify that nozzle bail is fully open during calibration
3. Follow instructions on SAM BOOST
Sheet: FSG-MNL-00234
INSTALLATION, OPERATING, & MAINTENANCE MANUAL
Nozzle Calibration process will open the discharge valve
associated with the nozzle and automatically increase line
pressure. Calibration must be performed with two people
require a large amount of water to calibrate. It is recommended to use draft or
hydrant intakes during calibrations. Shut off the tank to pump by pressing the –
button to close valve.