SAM BOOST™ WITH SMART NOZZLE N
7.8
SAM Smart Nozzle Flow Calibration (Password 10610)
1. Engage pump while inside calibration screen
a. SAM Boost™ will default the water source from the internal tank. The nozzles will
2. Wake up nozzle by pressing a button
a. Verify that nozzle bail is fully open during calibration
3. Follow instructions on SAM BOOST
Sheet: FSG-MNL-00234
INSTALLATION, OPERATING, & MAINTENANCE MANUAL
Nozzle Calibration process will open the discharge valve
associated with the nozzle and automatically increase line
pressure. Calibration must be performed with two people
require a large amount of water to calibrate. It is recommended to use draft or
hydrant intakes during calibrations. Shut off the tank to pump by pressing the –
button to close valve.
PHONE: (800) 288.1161
www.akronbrass.com
Revision 2023-08-28
P AND UV780 DISPLAY
2
TM
display
Page: 57 of 66