Sam Smart Nozzle Pairing (Password 10600) - Idex Akron Bras SAM BOOST Operation Installation Maintenance Manual

For sam boost with smart nozzle n2p and uv780 display
Table of Contents

Advertisement

SAM BOOST™ WITH SMART NOZZLE N
1. Prior to entering password cap and then open discharge valves to be calibrated.
2. Enter password 08267 to access valve calibration screen (shown above).
3. With no pressure on the lines, hit top right button SEND 0
a. Note that pressures will not properly update on screen until both zero and high
4. Increase pump pressure to a known high pressure (200 psi is recommended)
a. Pressure value to send can be adjusted with the +/- buttons on the screen
5. Hit the SEND HIGH button to send high pressure calibration point
6. Relieve valve pressure.
7. Power cycle the system
7.7

SAM Smart Nozzle Pairing (Password 10600)

Sheet: FSG-MNL-00234
INSTALLATION, OPERATING, & MAINTENANCE MANUAL
calibration are completed.