SAM BOOST™ WITH SMART NOZZLE N
4. Clean or replace if clogged.
9.5
Master Pressure Transducer Maintenance
It is recommended to calibrate the master discharge and intake pressure transducers annually. Please
follow procedure steps in the "Pressure Calibration Password" Section of this manual.
If a sensor is ever not performing appropriately, then remove sensor, inspect sensor and line for debris.
Clean out as needed.
9.6
Tank Level Sensor Maintenance
If the sensor is ever not performing appropriately, then remove sensor, inspect sensor and line for debris.
Clean out as needed.
If the tank level low warning isn't alarming at approximately a quarter tank, then the sensor may need to be
recalibrated. Follow the tank level calibration instruction in the password section of this manual.
Sheet: FSG-MNL-00234
INSTALLATION, OPERATING, & MAINTENANCE MANUAL
Action
Calibrate sensor
Clean out sensor
Action
Calibrate sensor
Clean out sensor
PHONE: (800) 288.1161
www.akronbrass.com
Revision 2023-08-28
P AND UV780 DISPLAY
2
Cadence
Annually
As Needed
Cadence
As Needed
As Needed
Page: 64 of 66